Time Response of the Frequency of Hydroelectric Generator Unit with Surge Tank Under Isolated Operation Based on Turbine Regulating Modes

被引:39
作者
Guo, Wencheng [1 ]
Yang, Jiandong [1 ]
Chen, Jieping [1 ]
Yang, Weijia [2 ]
Teng, Yi [1 ]
Zeng, Wei [1 ]
机构
[1] Wuhan Univ, State Key Lab Water Resources & Hydropower Engn S, Wuhan 430072, Hu Bei, Peoples R China
[2] Uppsala Univ, Dept Engn Sci, Uppsala, Sweden
基金
中国国家自然科学基金;
关键词
hydroelectric generator unit; surge tank; isolated operation; turbine regulating system; time response of the frequency; regulation quality; regulating mode; dominant pole; POWER-PLANT; LOAD; SYSTEM;
D O I
10.1080/15325008.2015.1082681
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Aiming at studying the regulation quality of isolated turbine regulating systems under load disturbance and different regulation modes, the complete mathematical model of a turbine regulating system under three regulation modes is established. Then, based on dominant poles and null points, the method of order reduction for a high-order system of time response of the frequency is proposed. By this method, the complete high-order systems are solved and the regulation quality for time response of the frequency is studied. The results indicate that (1) the tail wave, which is the main body of time response of the frequency and the principal factor that determines the regulation quality, is mainly determined by the dominant poles; (2) for the three regulation modes, by deleting the high-order terms, the three equivalent overall transfer functions are fourth order, third order, and third order, respectively, and can be solved; (3) the analytical fluctuation equations of time response of the frequency solved from low-order equivalent overall transfer functions accurately simulate the fluctuation characteristics of time response; and (4) based on damped vibrations decomposed from analytical fluctuation equations, the regulation qualities of three regulation modes are analyzed.
引用
收藏
页码:2341 / 2355
页数:15
相关论文
共 28 条
[1]  
[Anonymous], 1979, MATH HDB
[2]  
[Anonymous], POWER SYSTEM STABILI
[3]   Renewable energy sources and frequency regulation: survey and new perspectives [J].
Bevrani, H. ;
Ghosh, A. ;
Ledwich, G. .
IET RENEWABLE POWER GENERATION, 2010, 4 (05) :438-457
[4]  
Chaturvedi D. K., 1999, ELECT POWER ENERGY S, P405
[5]   HYDRAULIC-TURBINE AND TURBINE CONTROL-MODELS FOR SYSTEM DYNAMIC STUDIES [J].
DEMELLO, FP ;
KOESSLER, RJ ;
AGEE, J ;
ANDERSON, PM ;
DOUDNA, JH ;
FISH, JH ;
HAMM, PAL ;
KUNDUR, P ;
LEE, DC ;
ROGERS, GJ ;
TAYLOR, C .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :167-179
[6]   Load frequency control of an isolated small-hydro power plant with reduced dump load [J].
Doolla, Suryanarayana ;
Bhatti, T. S. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (04) :1912-1919
[7]  
Erturul C., 2007, ENERG CONVERS MANAG, P1281
[8]   Basic Modeling and simulation tool for analysis of hydraulic transients in hydroelectric power plants [J].
Fang, Hongqing ;
Chen, Long ;
Dlakavu, Nkosinathi ;
Shen, Zuyi .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2008, 23 (03) :834-841
[9]  
Franklin G., 2009, FEEDBACK CONTROL DYN
[10]  
[付亮 FU Liang], 2009, [水力发电学报, Journal of Hydroelectric Engineering], V28, P115