Parameter Identification Algorithm for Fault Location Based on Distributed Transmission Line model

被引:0
作者
Kang, Xiaoning [1 ]
Jiale, Suonan [1 ]
Bo, Zhiqian [3 ]
Tang, Jian [2 ]
Jun, Qi
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, Xian 710049, Peoples R China
[2] Huazhong Univ Sci & Technol, Coll Elect & Elect Engn, Wuhan 430074, Peoples R China
[3] AREVA T&D Automat, Stafford ST17 4LX, England
来源
2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11 | 2008年
关键词
fault location; parameter identification; one-terminal; time domain;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposed a novel time-domain fault location algorithm using one-terminal data. By using parameter identification method and distributed transmission line model, fault can be located with local voltage and current data. Since the fault distance, fault resistance and the remote terminal source parameters are considered as unknown variables, the time-domain equations of the fault-superimposed component network are solved to determine the fault distance. The technique uses two-dimensional search in the plane of fault distance and fault resistance. At any searching step, the two variables to be searched are assumed to be fixed values. Therefore, a series of remote terminal source parameters are calculated with moving data windows. In the end, both fault distance and fault resistance, with which the divergence from the calculated opposite source parameters is minimum, are regarded as the actual parameters. This algorithm eliminates influence of the fault resistance and the source parameters at the opposite end on the fault location accuracy, which has been the main cause of error for conventional one-terminal approaches. In addition, this algorithm uses the transient sampling data directly with short data window. The EMTP simulation results prove the validity and high accuracy of the new algorithm.
引用
收藏
页码:4098 / +
页数:3
相关论文
共 18 条
[1]  
Chen Ping, 2000, Proceedings of the CSEE, V20, P56
[2]  
Chen Zheng, 2003, Journal of Tsinghua University (Science and Technology), V43, P310
[3]  
Dong Xinzhou, 1999, Proceedings of the CSEE, V19, P76
[4]   A novel principle of single-ended fault location technique for EHV transmission lines [J].
Ha, HX ;
Zhang, BH ;
Lv, ZL .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) :1147-1151
[5]  
Heng-xu Ha, 2003, Proceedings of the CSEE, V23, P42
[6]   ACCURATE FAULT LOCATION TECHNIQUE FOR POWER TRANSMISSION-LINES [J].
JOHNS, AT ;
JAMALI, S .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1990, 137 (06) :395-402
[7]  
Li Zhimin, 1997, Proceedings of the CSEE, V17, P416
[8]  
Liang Jun, 1997, Automation of Electric Power Systems, V21, P24
[9]  
Mao Xiaoming, 1998, Power System Technology, V22, P15
[10]   Unsynchronized two-terminal fault location estimation [J].
Novosel, D ;
Hart, DG ;
Udren, E ;
Garitty, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) :130-138