Lightning Transients on Branched Distribution Lines Considering Frequency-Dependent Ground Parameters

被引:0
|
作者
De Conti, Alberto [1 ]
Alipio, Rafael [2 ]
机构
[1] Univ Fed Minas Gerais, LRC, Belo Horizonte, MG, Brazil
[2] CEFET MG Fed Ctr Technol Educ, DEE, Belo Horizonte, MG, Brazil
来源
2016 33RD INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP) | 2016年
关键词
transmission line modeling; frequency-dependent ground parameters; branched distribution lines; lightning overvoltages; INDUCED VOLTAGES; ELECTRICAL PARAMETERS; OVERHEAD LINES; MULTICONDUCTOR;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper investigates the influence of considering frequency-dependent ground parameters in the calculation of lightning transients on a two-phase distribution line including the presence of branches. The analysis is focused on propagation effects along the line. It is shown that the influence of frequency dependent ground parameters is only remarkable if a poorly conducting ground is considered. It is also shown that the presence of line branches is likely to reduce the relative importance of considering the frequency variation of the ground parameters in the calculation of lightning transients.