Dynamic modelling and thermoeconomic analysis of micro wind turbines and building integrated photovoltaic panels

被引:43
作者
Calise, Francesco [1 ]
Cappiello, Francesco Liberato [1 ]
D'Accadia, Massimo Dentice [1 ]
Vicidomini, Maria [1 ]
机构
[1] Univ Naples Federico II, DII, Ple Tecchio 80, I-80125 Naples, Italy
关键词
BIPV; Wind turbine; Heat pump; Dynamic simulation; RENEWABLE POLYGENERATION SYSTEM; POWER-SYSTEMS; ENERGY; DESIGN; SIMULATION; OPTIMIZATION; PERFORMANCE; WATER; CLIMATES; DIESEL;
D O I
10.1016/j.renene.2020.06.075
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
During the past few years a significant effort has been performed in order to promote the use of renewable energy sources. However, one of the main barriers for a mature commercialization is due to the unpredictability of the renewable power production, mainly in case of wind and solar energy. Unfortunately, electric storage devices are often poorly profitable. Therefore, some more stable renewable energy systems must be designed. In this framework, this paper presents a novel hybrid renewable system consisting of Building Integrated PhotoVoltaic panels and small-scale Wind Turbines and double stage heat pumps. This combination is very promising since it reduces the typical fluctuations of solar or wind systems, achieving a more stable profile of the overall power production. A detailed dynamic simulation model is developed in TRNSYS environment, including validated models for all the components and a suitable thermoeconomic analysis. A case study is implemented for a hotel building, where the space heating and cooling energy is supplied by an electrically driven reversible air-to-water Heat Pump, supplied by the electricity produced by Building Integrated PhotoVoltaic panels and Wind Turbines. the thermal energy recovered from the HP desuperheater is coupled with the thermal energy produced by a two-stage cascade cycle Heat Pump to produce domestic hot water. Results are presented in terms of hourly, monthly and yearly system performance data as well as by discussing the results of a detailed sensitivity analysis performed to detect the optimum configuration and weather zone of this hybrid renewable system. An analysis of the building envelope features is also performed, according to the nearly zero energy buildings target. Results showed that the combination of photovoltaic and wind technologies allows one to significantly enhance the stability of the renewable power production. Results also show that the use of heat pumps leads to a reduction of the primary energy demand for building space heating/cooling and domestic hot water by 30%. A payback period of about 5.2 years is obtained and the optimum configuration suggests adopting one 20 kW Wind Turbine for the selected case study. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页码:633 / 652
页数:20
相关论文
共 58 条
[1]   Techno-economic assessment and optimization of a hybrid renewable earth - air heat exchanger coupled with electric boiler, hydrogen, wind and PV configurations [J].
Akhtari, Mohammad Reza ;
Shayegh, Iman ;
Karimi, Nader .
RENEWABLE ENERGY, 2020, 148 :839-851
[2]   Model for calculating the sustainable building index (SBI) in the kingdom of Bahrain [J].
Alnaser, N. W. ;
Flanagan, R. ;
Alnaser, W. E. .
ENERGY AND BUILDINGS, 2008, 40 (11) :2037-2043
[3]   Design and performance evaluation based on economics and environmental impact of a PV-wind-diesel and battery standalone power system for various climates in Turkey [J].
Altun, Ayse Fidan ;
Kilic, Muhsin .
RENEWABLE ENERGY, 2020, 157 :424-443
[4]  
[Anonymous], 2015, TASK 40 EBC ANN 52 N
[5]  
[Anonymous], 2015, World Energy Outlook 2015
[6]  
[Anonymous], SOLAR ENGINEERING OF
[7]  
[Anonymous], 2013, SOLAR ENG THERMAL PR
[8]   Optimization of a building integrated solar thermal system with seasonal storage using TRNSYS [J].
Antoniadis, Christodoulos N. ;
Martinopoulos, Georgios .
RENEWABLE ENERGY, 2019, 137 :56-66
[9]   Urban wind conditions and small wind turbines in the built environment: A review [J].
Anup, K. C. ;
Whale, Jonathan ;
Urmee, Tania .
RENEWABLE ENERGY, 2019, 131 :268-283
[10]   A technical review of building-mounted wind power systems and a sample simulation model [J].
Ayhan, Dursun ;
Saglam, Safak .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2012, 16 (01) :1040-1049