Characteristic of Third Harmonic From Synchronous Generator Passing Through Transformer and Rectifier

被引:0
作者
Abdullah, M. F. [1 ]
Hamid, N. H. [1 ]
Baharudin, Z. [1 ]
Ayob, M. A. M. [1 ]
Hamim, M. A. F. M. [1 ]
机构
[1] Univ Teknol PETRONAS, Elect & Elect Engn Dept, Tronoh 31750, Perak, Malaysia
来源
2012 IEEE INTERNATIONAL CONFERENCE ON POWER AND ENERGY (PECON) | 2012年
关键词
Third harmonic voltage; third harmonic current; synchronous generator; transformer; rectifier;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The third harmonic has caused much power quality problem in the neutral of distribution system. Salient pole synchronous generator has been recognized as one of the triplen/third harmonic sources. This research is aimed at studying the characteristic of third harmonic from generator flowing through the load directly, via transformer and shunt connection to rectifier. Lab scale experiments have been conducted to vary load impedance and transformer winding configuration. When generator is connected directly to a combined resistive and inductive load, the third harmonic current and voltage depend on the load impedance magnitude and phase angle. Since the third harmonic voltage produced by generator are in phase or zero sequence in nature, the third harmonic current depend on transformer winding configuration, the load impedance magnitude and phase angle. When full-wave bridge rectifier is shunt connected between generator and load, the third harmonic current at both rectifier and load are actually coming from generator that depend on load impedance magnitude and phase angle. It is recommended that the study on third harmonic voltage and current propagation from generator should be done by performing harmonic measurement and analysis at all parts of the network. Third harmonic voltage and current magnitude alone may not give correct indication to their severity because they are vector quantity and rely on zero sequence network, load impedance magnitude and phase angle.
引用
收藏
页码:689 / 694
页数:6
相关论文
共 10 条
[1]  
Abdullah M. F., 2011, INT C EL ENG INF JUL
[2]  
Abdullah M. F., 2010, 9 INT POW EN C OCT
[3]  
Barnes R. H., 1989, IEE C SAF IND PLANT
[4]  
Brown WA, 2010, IND COMMER POWER
[5]   Interfacing Techniques for Time-Domain and Frequency-Domain Simulation Methods [J].
Chavez, Jose de Jesus ;
Ramirez, Abner I. ;
Dinavahi, Venkata ;
Iravani, Reza ;
Martinez, Juan A. ;
Jatskevich, Juri ;
Chang, Gary W. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (03) :1796-1807
[6]   Triplen harmonics: Myths and reality [J].
Chicco, Gianfranco ;
Postolache, Petru ;
Toader, Cornel .
ELECTRIC POWER SYSTEMS RESEARCH, 2011, 81 (07) :1541-1549
[7]   UPFC modeling in the harmonic domain [J].
Collins, C ;
Watson, N ;
Wood, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) :933-938
[8]   Analysis of Elevated Neutral-to-Earth Voltage in Distribution Systems With Harmonic Distortion [J].
Collins, Edward R. ;
Jiang, Jian .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1696-1702
[9]   A Time-Domain Harmonic Power-Flow Algorithm for Obtaining Nonsinusoidal Steady-State Solutions [J].
Lian, Kuo Lung ;
Noda, Taku .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (03) :1888-1898
[10]  
Smith J. J., 1930, T AM I ELECT ENG