Particulate concentrations within a reduced-scale room operated at various air exchange rates

被引:18
作者
Faulkner, W. Brock [1 ]
Memarzadeh, Farhad [2 ]
Riskowski, Gerald [1 ]
Hamilton, Keith [1 ]
Chang, Ching-Zu [3 ]
Chang, Jieh-Ren [3 ]
机构
[1] Texas A&M Univ, Biol & Agr Engn Dept, College Stn, TX 77843 USA
[2] NIH, Div Tech Resources, Bethesda, MD 20892 USA
[3] Natl Ilan Univ, Dept Food Sci, Ilan, Taiwan
关键词
Particulate concentrations; Variable air exchange rate; ACH; Ventilation system; Scaled chamber; No obstructions;
D O I
10.1016/j.buildenv.2013.03.023
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Precise prediction of particulate movement is needed to provide a better understanding of how airborne disease organisms move within ventilated facilities. Bacteria often adhere to larger airborne particulates, which will modify their movement behavior in ventilated rooms and may provide an environment to allow them to remain virulent longer. An empty chamber (206 H x 203 W x 386 cm L) with a circular air inlet and outlet on opposite ends was ventilated with air that had a known particulate density. The inlet and outlet openings were sized to maintain inlet and exit velocities at around 5.1 m/s at 5 different air exchange rates (around 2, 4, 5, 9, and 14 air changes per hour - ACH). Particulate concentrations were measured at the air outlet and at 12 locations within the chamber. In this study, the particulate concentration in the inlet air remained constant, so the amount of particulates injected into the chamber increased as the ACH increased. The measured particulate levels at the outlet also increased essentially linearly with an increase in ACH. However, the particulate concentrations in the occupied zone of the chamber did not increase linearly with an increase in actual ACH. Rather, it increased essentially linearly at the lower ACH levels (from around 2 to 5 ACH), but then leveled out at the higher ACH values. The advantages of increasing ACH in terms of providing better environments in the occupied zone of rooms may have limits, which warrant further investigation. (c) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:71 / 80
页数:10
相关论文
共 14 条
[1]  
[Anonymous], 2001, Guidelines for Design and Construction of Hospital and Health Care Facilities
[2]  
[Anonymous], ASHRAE HDB FUND
[3]  
Committee for the Update of the Guide for the Care and Use of Laboratory Animals, 2011, GUIDE CARE USE LAB A
[4]  
Duguid JP., 1945, Journal of Aerosol Science, V40, P256
[5]  
Faulkner WB, 2006, APPL ENG AGRIC, V22, P155
[6]   Health effects of airborne exposures from concentrated animal feeding operations [J].
Heederik, Dick ;
Sigsgaard, Torben ;
Thorne, Peter S. ;
Kline, Joel N. ;
Avery, Rachel ;
Bonlokke, Jakob H. ;
Chrischilles, Elizabeth A. ;
Dosman, James A. ;
Duchaine, Caroline ;
Kirkhorn, Steven R. ;
Kulhankova, Katarina ;
Merchant, James A. .
ENVIRONMENTAL HEALTH PERSPECTIVES, 2007, 115 (02) :298-302
[7]   An aerobiological perspective of dust in cage-housed and floor-housed poultry operations [J].
Just N. ;
Duchaine C. ;
Singh B. .
Journal of Occupational Medicine and Toxicology, 4 (1)
[8]  
Memarzadeh F., 2000, ASHRAE Transactions, V106, P731
[9]   Role of air changes per hour (ACH) in possible transmission of airborne infections [J].
Memarzadeh, Farhad ;
Xu, Weiran .
BUILDING SIMULATION, 2012, 5 (01) :15-28
[10]   Effect of reducing ventilation rate on indoor air quality and energy cost in laboratories [J].
Memarzadeh, Farhad .
JOURNAL OF CHEMICAL HEALTH & SAFETY, 2009, 16 (05) :20-26