Assessment and Choice of Input Signals for Multiple HVDC and FACTS Wide-Area Damping Controllers

被引:60
作者
Li, Yong [1 ]
Rehtanz, Christian [1 ]
Rueberg, Sven [1 ]
Luo, Longfu [2 ]
Cao, Yijia [2 ]
机构
[1] TU Dortmund Univ, Inst Energy Syst Energy Efficiency & Energy Econ, D-44227 Dortmund, Germany
[2] Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Hunan, Peoples R China
基金
美国国家科学基金会;
关键词
Flexible ac transmission system (FACTS); high-voltage direct current (HVDC) transmission; inter-area oscillations; relative gain array (RGA); residue analysis; wide-area damping controllers (WADCs); TIME-DELAY; POWER; PLACEMENT;
D O I
10.1109/TPWRS.2012.2189865
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a hybrid method to assess and select suitable control inputs for multiple HVDC and FACTS supplementary wide-area damping controllers (WADCs) of large-scale interconnected power system. This method can not only reduce the interaction among different WADCs, but also get good performance of damping multiple inter-area oscillations. The residue analysis method based on observability/controllability index is used to preselect the input signal candidates for each WADC. Then, the relative gain array (RGA) analysis, including the steady-state values and the dynamic behavior, is carried out to evaluate and determine the suitable input signals for multiple WADCs. Since the undesired interaction among multiple WADCs is reduced significantly by the proposed method, we can design each WADC independently without considering the coordination of controllers, which can reduce the design difficulty of multiple WADCs. A detailed case study validates the proposed method, and indicates that the multiple WADCs adopting the selected wide-area signals can effectively damp multiple inter-area oscillations at different operating scenarios (e. g., line fault, line outage, and load shedding).
引用
收藏
页码:1969 / 1977
页数:9
相关论文
共 14 条
[1]   Placement of SVCs and selection of stabilizing signals in power systems [J].
Farsangi, Malihe M. ;
Nezamabadi-pour, Hossein ;
Song, Yong-Hua ;
Lee, Kwang Y. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :1061-1071
[2]   Choice of FACTS device control inputs for damping interarea oscillations [J].
Farsangi, MM ;
Song, YH ;
Lee, KY .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (02) :1135-1143
[3]   Design and experiment of wide area HVDC supplementary damping controller considering time delay in China southern power grid [J].
He, J. ;
Lu, C. ;
Wu, X. ;
Li, P. ;
Wu, J. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2009, 3 (01) :17-25
[4]   Assessment of two methods to select wide-area signals for power system damping control [J].
Heniche, Annissa ;
Kamwa, Innocent .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (02) :572-581
[5]  
Kundur P., 1993, Power System Stability And Control
[6]   Robust high-voltage direct current stabilising control using wide-area measurement and taking transmission time delay into consideration [J].
Li, Y. ;
Rehtanz, C. ;
Yang, D. ;
Rueberg, S. ;
Haeger, U. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (03) :289-297
[7]  
Li Y., 2010, INT C POW SYST TECHN, P1, DOI DOI 10.1109/POWERCON.2010.5666549
[8]  
Liu F., 2010, 2010 9th International Conference on Environment and Electrical Engineering, Prague, Czech Republic, P313
[9]   Identification of electromechanical modes and placement of PSSs using relative gain array [J].
Milanovic, JV ;
Duque, ACS .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (01) :410-417
[10]   Optimal wide area controller and state predictor for a power system [J].
Mohagheghi, Salman ;
Venayagamoorthy, Ganesh K. ;
Harley, Ronald G. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (02) :693-705