External System Line Outage Identification Using Phasor Measurement Units

被引:37
作者
Emami, Roozbeh [1 ]
Abur, Ali [2 ]
机构
[1] Nexant Corp, Chandler, AZ 85226 USA
[2] Northeastern Univ, Dept Elect & Comp Engn, Boston, MA 02115 USA
关键词
External system; identification; line outage; phasor measurement units; state estimation; STATE ESTIMATION; TOPOLOGY ERRORS; POWER NETWORKS;
D O I
10.1109/TPWRS.2012.2220865
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper investigates the problem of line outage detection in an area external to the operating area boundaries. The so-called "internal system" is assumed to be fully observable and the base case topology of the external system is assumed to be known. A limited number of phasor measurements are also assumed to be available from the external system. The paper takes advantage of the equivalent representation of a line outage by a pair of injections at the line's terminal buses and formulates the outage detection problem as an integer programming problem. Results are verified by simulating various external line outage scenarios using the IEEE 118-bus test system.