A non-communication based protection algorithm for multi-terminal HVDC grids

被引:42
作者
Abu-Elanien, Ahmed E. B. [1 ,2 ]
Abdel-Khalik, Ayman S. [2 ,3 ]
Massoud, Ahmed M. [4 ]
Ahmed, Shehab [3 ]
机构
[1] Dhofar Univ, Elect & Comp Engn Dept, Salalah 211, Oman
[2] Univ Alexandria, Fac Engn, Dept Elect Engn, Alexandria, Egypt
[3] Texas A&M Univ, Elect & Comp Engn Dept, Doha, Qatar
[4] Qatar Univ, Coll Engn, Doha, Qatar
关键词
HVDC; Protection of multi-terminal HVDC; Wavelet transform; Wind farm; DROOP CONTROL DESIGN; OFFSHORE WIND FARM; FAULT LOCATION; VSC HVDC;
D O I
10.1016/j.epsr.2016.11.010
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces a non-communication based protection algorithm for Multi-Terminal High Voltage Direct Current (MTHVDC) transmission lines. The algorithm relies on using electrical current data at one end for identification of the fault zone without communication between relays. The concept is to use the fault generated transients to differentiate between internal and external faults. Shunt capacitors with predetermined values are installed at the boundary between each two HVDC line sections to assist, together with the busbar stray capacitance, in the classification of internal faults. The high frequency transients will reach the relaying point without any attenuation if the fault is internal; nevertheless, the high frequency transients will be highly attenuated if the fault is external due to the stray capacitance and the installed shunt capacitor at the connection busbar. Discrete Wavelet Transform (DWT) is used to analyze the fault current signals. MTHVDC system modeling and relay design are carried out in the MATLAB/SIMULINK environment. The results of the proposed algorithm were highly reliable regarding different types of faults with different fault resistances and at various locations. (C) 2016 Elsevier B.V. All rights reserved.
引用
收藏
页码:41 / 51
页数:11
相关论文
共 26 条
[1]   A Droop Control Design for Multiterminal HVDC of Offshore Wind Farms With Three-Wire Bipolar Transmission Lines [J].
Abdel-Khalik, Ayman S. ;
Abu-Elanien, Ahmed E. B. ;
Elserougi, Ahmed A. ;
Ahmed, Shehab ;
Massoud, Ahmed M. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (02) :1546-1556
[2]   Optimum Power Transmission-Based Droop Control Design for Multi-Terminal HVDC of Offshore Wind Farms [J].
Abdel-Khalik, Ayman S. ;
Massoud, Ahmed M. ;
Elserougi, Ahmed A. ;
Ahmed, Shehab .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (03) :3401-3409
[3]   A differential protection technique for multi-terminal HVDC [J].
Abu-Elanien, Ahmed E. B. ;
Elserougi, Ahmed A. ;
Abdel-Khalik, Ayman S. ;
Massoud, Ahmed M. ;
Ahmed, Shehab .
ELECTRIC POWER SYSTEMS RESEARCH, 2016, 130 :78-88
[4]  
[Anonymous], 2011, 2011 IEEE PES POW SY, DOI DOI 10.1109/PSCE.2011.5772604
[5]  
[Anonymous], 2013, POWERTECH IEEE, DOI DOI 10.1109/PTC.2013.6652480
[6]  
[Anonymous], 2012, PROC INT MULTICONF S
[7]   Fault location on multi-terminal DC systems using synchronized current measurements [J].
Azizi, Sadegh ;
Afsharnia, Saeed ;
Sanaye-Pasand, Majid .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 63 :779-786
[8]   A new non-communication protection technique for transmission lines [J].
Bo, ZQ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (04) :1073-1078
[9]  
Chaudhuri B., 2014, MULTITERMINAL DIRECT
[10]   A fault location criterion for MTDC transmission lines using transient current characteristics [J].
Cheng, Jingzhou ;
Guan, Minyuan ;
Tang, Lv ;
Huang, Hongyang .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 61 :647-655