A Case Study on the Application of the Nyquist Stability Criterion as Applied to Interconnected Loads and Sources on Grids

被引:80
作者
Turner, Robert [1 ,2 ]
Walton, Simon [2 ]
Duke, Richard [1 ]
机构
[1] Univ Canterbury, Dept Elect & Comp Engn, Christchurch 8020, New Zealand
[2] ABB, Power Qual Unit, Napier 4110, New Zealand
关键词
Bandwidth; control systems; inverters; power system stability; robust stability; stability; stability analysis; TORSIONAL INTERACTION; SYNCHRONOUS MACHINE; PASSIVITY; SYSTEMS;
D O I
10.1109/TIE.2012.2198031
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
As the penetration of complex grid-connected devices, such as power electronic inverters, increases, so too does the complexity of analyzing system stability. A graphical application of the Nyquist stability criterion is presented that indicates how an individual load and source each contribute to the closed-loop system grid eigenvalues. The case study is not limited to particular impedance forms or scenarios like the more common complex torque coefficient method or passivity theory method. From the individual frequency responses of the load and source impedances, the graphical technique indicates how each impedance contributes to the system stability. Examples are provided that successfully indicate the cause of instability for a digitally controlled voltage source inverter (VSI) operating as a microgrid, with a current source inverter as a load. A second example is provided that identifies the potential instability of a VSI running an induction machine. A 42-kW inverter system is used to confirm the findings, showing a close correlation with the theoretical analysis.
引用
收藏
页码:2740 / 2749
页数:10
相关论文
共 36 条
[1]   Current Controller Based on Reduced Order Generalized Integrators for Distributed Generation Systems [J].
Alberto Busada, Claudio ;
Gomez Jorge, Sebastian ;
Leon, Andres E. ;
Solsona, Jorge A. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2012, 59 (07) :2898-2909
[2]  
Belkhayat M., 1997, Stability criteria for AC power systems with regulated loads
[3]   MULTIVARIABLE NYQUIST CRITERIA, ROOT LOCI, AND POLE PLACEMENT - A GEOMETRIC VIEWPOINT [J].
BROCKETT, RW ;
BYRNES, CI .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 1981, 26 (01) :271-284
[4]   Probabilistic Analysis of Small-Signal Stability of Large-Scale Power Systems as Affected by Penetration of Wind Generation [J].
Bu, S. Q. ;
Du, W. ;
Wang, H. F. ;
Chen, Z. ;
Xiao, L. Y. ;
Li, H. F. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (02) :762-770
[5]   A NOVEL-APPROACH TO THE TORSIONAL INTERACTION AND ELECTRICAL DAMPING OF THE SYNCHRONOUS MACHINE .2. APPLICATION TO AN ARBITRARY NETWORK [J].
CANAY, IM .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (10) :3639-3647
[6]   A NOVEL-APPROACH TO THE TORSIONAL INTERACTION AND ELECTRICAL DAMPING OF THE SYNCHRONOUS MACHINE .1. THEORY [J].
CANAY, IM .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (10) :3630-3638
[7]  
Dahal S., 2009, P IEEE AUPEC AD SA A, P1
[8]   Augmenting Wind Power Penetration and Grid Voltage Stability Limits Using ESS: Application Design, Sizing, and a Case Study [J].
Ha Thu Le ;
Santoso, Surya ;
Thang Quang Nguyen .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (01) :161-171
[9]   Input-admittance calculation and shaping for controlled voltage-source converters [J].
Harnefors, Lennart ;
Bongiorno, Massimo ;
Lundberg, Stefan .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (06) :3323-3334
[10]   Modeling of three-phase dynamic systems using complex transfer functions and transfer matrices [J].
Harnefors, Lennart .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (04) :2239-2248