Fouling detection in a heat exchanger by observer of Takagi-Sugeno type for systems with unknown polynomial inputs

被引:29
作者
Delrot, Sabrina [1 ,2 ]
Guerra, Thierry Marie [1 ,2 ]
Dambrine, Michel [1 ,2 ]
Delmotte, Francois [3 ]
机构
[1] Univ Valenciennes & Hainaut Cambresis, LAMIH, F-59313 Valenciennes, France
[2] CNRS, UMR 8201, F-59313 Valenciennes, France
[3] Fac Sci Appl, LG2IA, F-62400 Bethune, France
关键词
Heat exchanger; Fouling; Nonlinear observer; Fuzzy Takagi-Sugeno models; Estimation; Lyapunov function; FUZZY CONTROL; DESIGN; MODELS;
D O I
10.1016/j.engappai.2012.08.004
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper proposes a new method for fouling detection in a heat exchanger. It is based on the modeling of the system in a fuzzy Takagi-Sugeno representation derived from a physical model. With this representation, the design of a fuzzy observer with unknown inputs of polynomial types is obtained via a LMI formulation. Main advantages of the proposed method are that neither specific sensor, excepted standard ones, nor special operating conditions such as steady state regime are required. Some realistic simulations show the efficiency of the proposed technique. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1558 / 1566
页数:9
相关论文
共 28 条
[1]  
[Anonymous], P FUZZ IEEE BARC SPE
[2]  
[Anonymous], STUDIES FUZZINESS SO
[3]  
[Anonymous], P INT S DISTR HEAT S
[4]  
[Anonymous], PARAMETER ESTIMATION
[5]  
[Anonymous], 1994, STUDIES APPL NUMERIC
[6]  
[Anonymous], P INT S DISTR HEAT S
[7]  
[Anonymous], P 6 INT C HEAT EXCH
[8]  
[Anonymous], 2007, Int. J. Heat Exch
[9]  
[Anonymous], P 19 INT S TRANSP PH
[10]  
[Anonymous], P 6 INT C HEAT EXCH