Finite Element Method to Construct a Lumped Parameter Ladder Network of the Transformer Winding

被引:0
作者
Chaouche, Moustafa Sahnoune [1 ]
Houassine, Hamza [1 ]
Moulahoum, Samir [1 ]
Colak, Ilhami [2 ]
机构
[1] Univ Medea, Res Lab Elect Engn & Automat LREA, Medea, Algeria
[2] Nisantasi Univ, Engn & Architecture Fac, Istanbul, Turkey
来源
2017 IEEE 6TH INTERNATIONAL CONFERENCE ON RENEWABLE ENERGY RESEARCH AND APPLICATIONS (ICRERA) | 2017年
关键词
transformer winding; finite element method; axial deformation; frequency response analysis FRA; SHORT-CIRCUIT; DEFORMATION; FREQUENCY; FORCES; MODEL;
D O I
暂无
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Power transformers are one of the critical points in the renewable energies networks for the transport and distribution of the electric energy. As a result, the diagnosis of transibrmers is necessary to ensure the reliability and service life. The frequency behavior of the transformer winding is generally studied using a high-frequency model to diagnose the various damages of the winding. For this purpose, this paper discusses the application of the finite element method (FEM) to construct a lumped parameters ladder network of an actual transformer winding. The investigated coil is discretized in five (05) identical sections that includes 30 turns for each. In addition, after the experimental validation of the adopted model, a diagnostic study to the axial deformations of the transformer winding was made using the parameters analysis of the detailed model and the transfer function obtained from the FRA test.
引用
收藏
页码:1092 / 1096
页数:5
相关论文
共 37 条
[1]   A Novel Online Technique to Detect Power Transformer Winding Faults [J].
Abu-Siada, A. ;
Islam, Syed .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) :849-857
[2]  
Ahmed K. IL, REN EN RES APPL ICRE, P820
[3]   Modified transformer winding ladder network model to assess non-dominant frequencies [J].
Ahour, Jafar Nosratian ;
Seyedtabaie, Saeed ;
Gharehpetian, Gevork B. .
IET ELECTRIC POWER APPLICATIONS, 2017, 11 (04) :578-585
[4]   Identification of power transformer models from frequency response data: A case study [J].
Akcay, H ;
Islam, SM ;
Ninness, B .
SIGNAL PROCESSING, 1998, 68 (03) :307-315
[5]  
An Hyeong Seung, 2014 INT C REN EN RE, P147
[6]  
[Anonymous], 2013, IEEE POW ENER SOC GE
[7]   Experimental investigation on terminal connection and system function pair during SFRA testing on three phase transformers [J].
Arumugam, Saravanakumar .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 58 :101-110
[8]  
Barzola J., 2016, INT J RENEWABLE ENER, V6
[9]  
Benkercha Rabah, POW EL MOT CONTR C P, P442
[10]  
Biberoglu Muhammet, REN EN RES APPL ICRE, P983