Directional relaying for double circuit line with series compensation

被引:34
作者
Biswal, Monalisa [1 ]
Pati, Bibhuti Bhusan [1 ]
Pradhan, Ashok Kumar [2 ]
机构
[1] Veer Surendra Sai Univ Technol, Dept Elect Engn, Sambalpur 768018, Odisha, India
[2] Indian Inst Technol, Dept Elect Engn, Kharagpur 721302, W Bengal, India
关键词
DISTANCE RELAY; SYSTEM; PROTECTION;
D O I
10.1049/iet-gtd.2012.0602
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a directional relaying algorithm for the protection of double circuit line with series capacitor is presented. The method uses four classifiers based on positive and negative sequence components which are combined with a voting technique to derive the direction of fault. The technique is evaluated using data simulated with electromagnetic transients including DC/power system computer added design (EMTDC/PSCAD) for a series compensated double circuit line. Results for voltage inversion, current inversion, high resistance far end fault, single pole tripping and cross country fault are presented. The proposed technique is found to be accurate.
引用
收藏
页码:405 / 413
页数:9
相关论文
共 26 条
[1]  
Alexander G.E., GER-3736
[2]  
Alture H.J., 2008, ADV SERIES COMPENSAT, VTP6340-01, P1
[3]  
[Anonymous], P 33 ANN W PROT REL
[4]  
Apostolov A., 2007, P 60 ANN C PROT REL, P85
[5]  
Calero F., PRACTICAL CONSIDERAT
[6]  
Calero F., 2008, MUTUAL IMPEDANCE PAR, P1
[7]  
Elmore A.Walter., 2003, PROTECTIVE RELAYING, VSecond
[8]   Design and evaluation of a directional algorithm for transmission-line protection based on positive-sequence fault components [J].
Gao, H. ;
Crossley, P. A. .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2006, 153 (06) :711-718
[9]   Method to improve digital distance relay impedance measurement when used in series compensated lines protected by a metal oxide varistor [J].
Ghassemi, F ;
Goodarzi, J ;
Johns, AT .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1998, 145 (04) :403-408
[10]   A DIGITAL PROTECTION TECHNIQUE FOR PARALLEL TRANSMISSION-LINES USING A SINGLE RELAY AT EACH END [J].
GILANY, MI ;
MALIK, OP ;
HOPE, GS .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :118-125