Analysis of the Influence of Installing Synchronous Condenser in HVDC Inverter Station to Receiving End Grid

被引:0
作者
Min, Fu [1 ]
Yin Zhaoyang [1 ]
Hai, Yan [1 ]
Cui Cancan [1 ]
机构
[1] Harbin Univ Sci & Technol, Sch Elect & Elect Engn, Harbin, Peoples R China
来源
2019 22ND INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS 2019) | 2019年
关键词
synchronous condenser; HVDC; weak receiving grid; operating characteristics; commutation failure;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As multi-infeed HVDC systems are fed into the AC grid, the problem of insufficient dynamic power reserve and insufficient voltage support of receiving-end grid is increasingly prominent. Short-circuit capacity and short-circuit ratio of the system, transient voltage level, and DC commutation failure probability before and after the installation of synchronous condenser are compared by simulation. The results prove the application effect of synchronous condenser in HVDC inverter station. Combined with the operating characteristics of synchronous condenser, the law of system voltage recovery time changing with transient time constant is revealed. The research provides a theoretical basis for dynamic reactive power compensation of synchronous condenser in HVDC inverter station.
引用
收藏
页码:4105 / 4109
页数:5
相关论文
共 33 条
[31]   Analysis of transient electromagnetic force on end windings of 300 Mvar synchronous condenser during dynamic reactive power compensation process [J].
Jing, Bingjie ;
Ling, Yanping ;
Wang, Dongmei ;
Zhu, Erhang ;
Han, Xiao .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 155
[32]   Global Transient Flow and Heat Analysis of Synchronous Condenser Based on Dichotomy Iteration and NITA Method Under Voltage Drop in Power Grid [J].
Wang, Likun ;
Song, Xusheng ;
Kou, Baoquan ;
Sun, Yutian ;
Shen, Fengyu ;
Li, Jingyan .
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2024, 44 (20) :8292-8303
[33]   Influence Mechanism Analysis of the Active Power Recovery Rate of HVDC on the Rotor Angle Stability of the Sending-end System [J].
Zhang Y. ;
Ding M. ;
Han P. ;
Sun H. ;
Yang W. ;
Chen Z. .