A Wavelet-ANN Technique for Locating Switched Capacitors in Distribution Systems

被引:16
作者
Abu-Elanien, Ahmed E. B. [1 ]
Salama, M. M. A. [1 ]
机构
[1] Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada
关键词
Power quality (PQ); switched capacitors; wavelet transform; TRANSFORM;
D O I
10.1109/TPWRD.2008.2002675
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With an increase in usage of sensitive electronic loads and adjustable speed drives, utilities and customers have paid more attention to power-quality (PQ) problems. Shunt capacitor switching is one of the PQ problems that causes a wide band of high-frequency transients in voltage and current signals which harmfully affect these types of sensitive loads. This paper presents an efficient technique for locating switched capacitors in the industrial distribution systems using discrete wavelet transform (DWT) integrated with a feedforward artificial neural network (FFANN). The technique relays on combining the three-phase currents at the customer side to construct one modal current signal, and then the DWT is used to capture the high-frequency current transients contained in this modal signal. The energy contained in the high-frequency current transients and the transient duration, converted into the number of samples, for two DWT decomposition levels, is used to feed an FFANN to classify the switched capacitor. The simulations are performed using PSCAD/EMTDC and the results are then interfaced to MATLAB, where the technique is implemented. It is found that the technique gives reliable results for locating switched capacitors.
引用
收藏
页码:400 / 409
页数:10
相关论文
共 16 条
  • [1] An efficient approach for tracking transients generated by utility shunt capacitor switching
    Chang, GW
    Shih, MH
    Chu, SY
    Thallam, R
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) : 510 - 512
  • [2] El-Saadany EF, 2001, CANADIAN CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING 2001, VOLS I AND II, CONFERENCE PROCEEDINGS, P869, DOI 10.1109/CCECE.2001.933555
  • [3] ELASADANY EF, 2001, P TRANSM DISTR C EXP, V1, P427
  • [4] HARMONICS AND TRANSIENT OVERVOLTAGES DUE TO CAPACITOR SWITCHING
    GIRGIS, AA
    FALLON, CM
    RUBINO, JCP
    CATOE, RC
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1993, 29 (06) : 1184 - 1188
  • [5] Locating switched capacitor using wavelet transform and hybrid principal component analysis network
    Hong, Ying-Yi
    Chen, Bo-Yuan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (02) : 1145 - 1152
  • [6] IEEE, Standard 399 T-1997
  • [7] A time-domain procedure for locating switched capacitors in power distribution systems
    Kim, J
    Grady, WM
    Arapostathis, A
    Soward, JC
    Bhatt, SC
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) : 1044 - 1049
  • [8] KIM J, 2000, P IEEE POW ENG SOC S, V2, P945
  • [9] A study on the application of wavelet analysis to power quality
    Kopparapu, C
    Chandrasekaran, A
    [J]. THIRTIETH SOUTHEASTERN SYMPOSIUM ON SYSTEM THEORY (SSST), 1998, : 350 - 353
  • [10] Usage of wavelet transform in the protection.of series-compensated transmission lines
    Megahed, Ashraf I.
    Moussa, A. Monem
    Bayoumy, A. E.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) : 1213 - 1221