A new algorithm for localization of radial deformation and determination of deformation extent in transformer windings

被引:31
作者
Karimifard, R. [1 ]
Gharehipetian, G. B. [1 ]
机构
[1] Amirkabir Univ Technol, Dept Elect Engn, Tehran 15914, Iran
关键词
transformer winding; deformation; buckling; transfer function; detection;
D O I
10.1016/j.epsr.2008.02.017
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The transfer function method is a reliable too] for the detection of the transformer winding deformation and displacement, but determining the extent of winding deformation without considering its location results in unreliable estimations. In addition, there is no exact method for detecting the location of deformation in the transformer windings. This paper suggests an algorithm to determine the extent of the winding buckling based on the detection of the deformation location. The paper presents two main points. The first one is a method for the localization of the radial deformation and the second one is a new index for the determination of the extent of the buckling in transformer windings. Simulation of the detailed model of homogenous and inhomogeneous windings verifies the validity of the proposed algorithm. (C) 2008 Elsevier B.V. All rights reserved.
引用
收藏
页码:1701 / 1711
页数:11
相关论文
共 10 条
[1]  
Bjerkan E., 2005, THESIS TRONDHEIM
[2]   Procedures for detecting winding displacements in power transformers by the transfer function method [J].
Christian, J ;
Feser, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :214-220
[3]  
DELEON F, 1994, IEEE T POWER DELIVER, V9, P231, DOI 10.1109/61.277694
[4]  
Gharehpetian G.B., 1996, THESIS RWTH AACHEN A
[5]   Hybrid modelling of inhomogeneous transformer windings for very fast transient overvoltage studies [J].
Gharehpetian, GB ;
Mohseni, H ;
Moller, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (01) :157-163
[6]   Monitoring of power transformers using the transfer function method [J].
Leibfried, T ;
Feser, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (04) :1333-1341
[7]   An efficient method to compute transfer function of a transformer from its equivalent circuit [J].
Ragavan, K ;
Satish, L .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :780-788
[8]   Transfer function method to diagnose axial displacement and radial deformation of transformer windings [J].
Rahimpour, E ;
Christian, J ;
Feser, K ;
Mohseni, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (02) :493-505
[9]  
Rahimpour E., 2001, THESIS U STUTTGART
[10]   An effort to understand what factors affect the transfer function of a two-winding transformer [J].
Satish, L ;
Sahoo, SK .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1430-1440