In order to prevent the surface breakdown of the basin-type insulator, it is important to optimize its surface electric field distribution. In this paper, a time-resolved model for simulating the electric field distribution of GIS bus duct was presented based on the finite difference time domain method. The electric field distribution of two typical 500 kV GIS bus ducts including the L-type busbar and T-type busbar were calculated. The electric field oscillation due to the effect of GIS geometry was analyzed under different time to crest voltage waveforms. The electric field strength of different locations on the surface of the basin-type insulators were obtained for the two typical structures. Simulation result shows that, for a 500 kV GIS bus duct, when the rise time of applied voltage is less than 4 ns, the peak value of the surface electric field strength of the basin-type insulator is 1.13 much as large as that of the steady-state case. The electric field strength on the surface of the insulator near the inner conductor is the largest. Under the action of a 50 ns ramp wave, the waveform is almost not oscillating and slowly reaches the steady state value. It is recommended that the dynamic electric field characteristics should be taken into account in the insulation design of GIS basin-type insulators.
引用
收藏
页数:4
相关论文
共 23 条
  • [1] Electric Field Distribution of UHVAC Basin-type Insulator with Very Fast Transient Overvoltage in GIS
    Wu, Zehua
    Wang, Haoran
    Tian, Huidong
    Shi, Ran
    Zhou, Shiyi
    Peng, Zongren
    Zhang, Pengfei
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 570 - 573
  • [2] Influence of Switching Conditions on Very Fast Transient Over-voltage in 500kV Gas Insulated Substation
    Liu, Qing
    Zhang, Yufeng
    ICEMS 2008: PROCEEDINGS OF THE 11TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1- 8, 2008, : 4451 - 4454
  • [3] Research on Lightning Over-voltage Protection for 500kV GIS Substation
    Wang, Zhuo
    Li, Lei
    Gan, Ling Xia
    Li, Ning
    Li, Hong Tao
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3501 - 3505
  • [4] A calculation method of transient field under very fast transient over-voltage in gas insulated substation (GIS)
    Gao, YH
    Yuan, H
    Wang, EZ
    Cao, YD
    APPLIED ELECTROMAGNETICS (III), 2001, 10 : 215 - 218
  • [5] Measurement of very fast transient overvoltage in 500kV GIS
    Sun, Wei
    Wang, Yun
    Wu, Zengyao
    Shi, Baozhuang
    Zhang, Wenyuan
    Gaoya Dianqi/High Voltage Apparatus, 34 (04): : 11 - 14
  • [6] Calculation of very fast transient over-voltage and its distribution in transformer windings in 110kV GIS
    Gao, YH
    Yuan, H
    Wang, EZ
    Cao, YD
    ICEMS'2001: PROCEEDINGS OF THE FIFTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS I AND II, 2001, : 208 - 211
  • [7] Research on Protection Measure for Very Fast Transient Over-voltage of GIS
    Li, Hongsheng
    Gan, Lingxia
    Li, Lei
    Zhou, Yuanyuan
    Xu, Yinfeng
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3506 - +
  • [8] The Effect of GIS Apparatus Parameter on Very Fast transient Over-voltage
    Meng Tao
    Lin Xin
    Xu Jianyuan
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 292 - 295
  • [9] Study of protection of transformer from very fast transient over-voltage in 750kV GIS
    Liu, Q
    ICEMS 2005: Proceedings of the Eighth International Conference on Electrical Machines and Systems, Vols 1-3, 2005, : 2153 - 2156
  • [10] Simulation of Radial Electric Field and Voltage Distribution of 500kV MOA Under Different Conditions of Pollution
    Zhang, Pipei
    Shi, Wei
    Li, Jie
    Sun, Jingwen
    Sun, Yandi
    Sun, Chenghai
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 272 - 276