Negative-Sequence Network Based Fault Location Scheme for Double-Circuit Multi-Terminal Transmission Lines

被引:51
作者
Ghorbani, Amir [1 ]
Mehrjerdi, Hasan [2 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, Abhar 4561934367, Iran
[2] Qatar Univ, Dept Elect Engn, Doha 2713, Qatar
关键词
Fault location; fault resistance; double-circuit multi-terminal transmission lines; negative-sequence network; ALGORITHM; PROTECTION;
D O I
10.1109/TPWRD.2019.2906056
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The fault resistance and infeeded currents from tapped transmission lines are the two main challenges to establish correct fault location estimation in multi-terminal transmission lines. Also, fault location estimation in double-circuit lines is more complicated than single-circuit lines due to the effect of mutual coupling and inter-circuit faults. This paper proposes a negativesequence network-based method to estimate the fault location of double-circuit multi-terminal transmission lines. In the presented method, signals are measured in the relay location and then, communication links are not required as it uses only one end measurements. Also, in conventional distance relays, six elements are needed to calculate the fault location in all types of faults. Furthermore, in this method, by using only one element for each transmission line, accurate fault location can be estimated. Also, high fault resistance, mutual coupling, and infeeded currents from tapped transmission lines do not have impact on the performance of the presented scheme. To investigate the effects of the line shunt capacitances on the proposedmethod, a PImodel of the transmission lines is used in all the investigations. Simulation results carried out usingMATLAB software indicate that the proposed scheme is able to produce excellent performance for the fault location estimation.
引用
收藏
页码:1109 / 1117
页数:9
相关论文
共 16 条
[1]   Synchrophasor-based backup distance protection of multi-terminal transmission lines [J].
Al-Emadi, Nasser A. ;
Ghorbani, Amir ;
Mehrjerdi, Hasan .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (13) :3304-3313
[2]   A Novel Algorithm for Locating Faults on Transposed/Untransposed Transmission Lines Without Utilizing Line Parameters [J].
Apostolopoulos, Christos A. ;
Korres, George N. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2328-2338
[3]   New fault-location method for a single multiterminal transmission line using synchronized phasor measurements [J].
Brahma, Sukumar M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1148-1153
[4]   Ground distance relay compensation based on fault resistance calculation [J].
Eissa, M. M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (04) :1830-1835
[5]   A Novel Back Up Wide Area Protection Technique for Power Transmission Grids Using Phasor Measurement Unit [J].
Eissa, M. M. ;
Masoud, M. Elshahat ;
Elanwar, M. Magdy Mohamed .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) :270-278
[6]   Accurate Single-Phase Fault-Location Method for Transmission Lines Based on K-Nearest Neighbor Algorithm Using One-End Voltage [J].
Farshad, Mohammad ;
Sadeh, Javad .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) :2360-2367
[7]   Digital fault location for parallel double-circuit multi-terminal transmission lines [J].
Funabashi, T ;
Otoguro, H ;
Mizuma, Y ;
Dube, L ;
Ametani, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (02) :531-537
[8]   Distance-differential protection of transmission lines connected to wind farms [J].
Ghorbani, Amir ;
Mehrjerdi, Hasan ;
Al-Emadi, Nasser A. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2017, 89 :11-18
[9]   A Fault Location Algorithm Based on Circuit Analysis for Untransposed Parallel Transmission Lines [J].
Kang, Sang-Hee ;
Ahn, Yong-Jin ;
Kang, Yong-Cheol ;
Nam, Soon-Ryul .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) :1850-1856
[10]   An Algorithm for Locating Faults in Three-Terminal Multisection Nonhomogeneous Transmission Lines Using Synchrophasor Measurements [J].
Lin, Tzu-Chiao ;
Lin, Pei-Yin ;
Liu, Chih-Wen .