Load Angle Based Loss of Excitation Protection Scheme for Parallel Connected Synchronous Generators

被引:3
作者
Rostami, Ali [1 ]
Rezaei, Navid [1 ]
Jalilian, Amin [2 ]
Naderi, Behzad [3 ]
Negnevitsky, Michael [3 ]
机构
[1] Univ Kurdistan, Dept Elect Engn, Sanandaj 1517566177, Iran
[2] Univ Wollongong, Australian Power Qual & Reliabil Ctr, Wollongong, NSW 2500, Australia
[3] Univ Tasmania, Ctr Renewable Energy & Power Syst, Hobart, Tas 7005, Australia
关键词
Impedance-based relay; load angle; loss-of-excitation (LOE); synchronous generators (SGs) protection; FIELD PROTECTION; SECURE;
D O I
10.1109/TIA.2022.3193987
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The main weaknesses of impedance-based loss-of-excitation (LOE) relay are its maloperation during the power system disturbances (PSDs) and its long detection time during LOE events. In this article, to tackle the mentioned problems, a new LOE protection scheme is proposed based on load angle (delta) variation of parallel synchronous generators (SGs) connected to a point of connection (POC). It will be shown that during a PSD, the variation of delta for all parallel SGs is similar such that their delta increases or decreases simultaneously. However, it will be shown that when the LOE occurs for one of the parallel SGs, the delta of faulty SG increases while other SGs will experience reduction in their delta. Hence, when more than one SG is connected to a POC, the LOE event can be discriminated from PSDs. In the proposed scheme, when one SG is connected to the grid, the impedance-based relay is employed to enable the developed method to detect LOE/PSD. Since in a real-world application, the outage rate of the parallel SGs in a power plant during the emergency situations, periodic services, etc., is very low on a yearly basis, the contribution of the impedance relay in the proposed scheme is quite limited to some special circumstances. Comprehensive simulation studies have been conducted in MATLAB/Simulink environment (R2017b); the results prove high efficiency of the proposed scheme.
引用
收藏
页码:6960 / 6969
页数:10
相关论文
共 29 条
[21]   Analytical technique for synchronous generator loss-of-excitation protection [J].
Noroozi, Naser ;
Yaghobi, Hamid ;
Alinejad-Beromi, Yoosef .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (09) :2222-2231
[22]   A Relay Logic for Total and Partial Loss of Excitation Protection in Synchronous Generators [J].
Rasoulpour, Mahdi ;
Amraee, Turaj ;
Sedigh, Ali Khaki .
IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (03) :1432-1442
[23]  
Reimert Donald., 2006, PROTECTIVE RELAYING
[24]  
Rostami A., 2021, P IEEE INT C SMART T, P1
[25]   Improvement of the impedance-based loss-of-field protection scheme based on the dynamic behavior of the synchronous generators [J].
Rostami, Ali ;
Rezaei, Navid .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 141
[26]   A reliable and straightforward index to avoid nuisance trip of the conventional Z-based loss-of-field relay in synchronous generators [J].
Rostami, Ali ;
Rezaei, Navid .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2022, 16 (06) :1201-1211
[27]   A Novel Loss-of-Excitation Protection Strategy Based on Reactive Power Increment of Synchronous Generators [J].
Rostami, Ali ;
Rezaei, Navid .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (06) :3733-3742
[28]   Fast and reliable index to protect the synchronous generators against loss of field incidence [J].
Rostami, Ali ;
Rezaei, Navid .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (24) :6019-6026
[29]  
Seifi H, 2011, POWER SYST, P1, DOI 10.1007/978-3-642-17989-1