Thermal Performance of Sub-Atmospheric Loop Thermosyphon with and without Enhanced Boiling Surface

被引:0
作者
Chang, S. W. [1 ]
Chiang, K. F. [2 ]
Huang, C. -C. [3 ]
机构
[1] Natl Kaohsiung Marine Univ, Thermal Fluids Lab, 142 Hai Chuan Rd, Kaohsiung 811, Taiwan
[2] Asia Vital Components Co Ltd, CEO Off, Taipei 24892, Taiwan
[3] Asia Vital Components Co Ltd, R&D Off, Taipei 24892, Taiwan
来源
2012 28TH ANNUAL IEEE SEMICONDUCTOR THERMAL MEASUREMENT AND MANAGEMENT SYMPOSIUM (SEMI-THERM) | 2012年
关键词
Two Phase Loop Thermosyphon; Enhanced Boiling Surface; 2-PHASE THERMOSIPHON; HEAT-TRANSFER; FLOW REGIME; EVAPORATOR; INSTABILITY; PIPES;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This experimental study comparatively examines the thermal performances of two-phase loop thermosyphons (TPLP) with and without enhanced boiling surface at sub-atmospheric pressures. The boiling instabilities along with the constituent and total thermal resistances of these TPLPs are analyzed with the aid of boiling flow structures imaged at sub-atmospheric pressures. Boiling heat flux (Q) and thermal resistance of condenser (R-th,R-con) are selected as the controlling parameters with their individual and interdependent effects on the thermal performances examined. With the present enhanced boiling surface, the intermittent bursting of large bubbles from liquid pool in the multi-channel evaporator of plain surface is significantly suppressed, leading to the moderate pressure waves agitated by bubble eruptions with reduced boiling instabilities and pressure-drop thermal resistances (R-th,R-Delta P). The effects of TPLP height (H), which affects the driven pressure head for liquid-vapor circulation, on the thermal performances of the enhanced TPLP at various Q and R-th,R-con are subsequently examined. Total thermal resistances (R-th) measured from the TPLTs with enhanced boiling surface are considerably reduced from the TPLTs with plain boiling surface and reduced to about 0.265 at the test condition of Q=150W, R-th,R-con=0.2, H=35.3 tube diameters. A set of R-th correlation which permits the evaluation of individual and interdependent Q, R-th,R-con and H impacts on total thermal resistances of the enhanced TPLPs is generated to assist the design activities using this type of enhanced TPLP for cooling of electronic chipsets.
引用
收藏
页码:45 / 51
页数:7
相关论文
共 19 条
  • [1] Boiling and evaporation in small diameter channels
    Bergles, AE
    Lienhard, JH
    Kendall, GE
    Griffith, P
    [J]. HEAT TRANSFER ENGINEERING, 2003, 24 (01) : 18 - 40
  • [2] Bowers M.B., 1994, ASME J ELECT PACKAGI, V116, P298
  • [3] Influence of spiky twisted tape insert on thermal fluid performances of tubular air-water bubbly flow
    Chang, Shyy Woei
    Lees, Arthur William
    Chang, Hsien-Tsung
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2009, 48 (12) : 2341 - 2354
  • [4] Forced convective flow and heat transfer of upward cocurrent air-water slug flow in vertical plain and swirl tubes
    Chang, Shyy Woei
    Yang, Tsun Lirng
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2009, 33 (07) : 1087 - 1099
  • [5] Fantozzi F, 2004, SUPERLATTICE MICROST, V35, P339, DOI 10.1016/j.spmi.2003.01.007
  • [6] Fukano T., 1987, JSME INT J B-FLUID T, V53, P1065
  • [7] Corresponding states correlation for maximum heat flux in two-phase closed thermosyphon
    Golobic, I
    Gaspersic, B
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1997, 20 (06): : 402 - 410
  • [8] Fundamental issues related to flow boiling in minichannels and microchannels
    Kandlikar, SG
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2002, 26 (2-4) : 389 - 407
  • [9] Understanding operational regimes of closed loop pulsating heat pipes: an experimental study
    Khandekar, S
    Dollinger, N
    Groll, M
    [J]. APPLIED THERMAL ENGINEERING, 2003, 23 (06) : 707 - 719
  • [10] Pressure drop in riser and evaporator in an advanced two-phase thermosyphon loop
    Khodabandeh, R