A New Inrush Current Identification Algorithm Based on Transformer Core Saturation

被引:0
|
作者
Jin, Ming [1 ]
Liu, Yuanlong [2 ]
机构
[1] GE Grid Software Solut, Redmond, WA 98052 USA
[2] Shandong Elect Power Dispatching & Control Ctr, Jinan 250001, Shandong, Peoples R China
来源
2017 IEEE POWER & ENERGY SOCIETY GENERAL MEETING | 2017年
关键词
Flux Restrained Current Differential Relay; Inrush Current Identification; Percentage Restrained Differential Protection; Power Transformer Protection; DIFFERENTIAL RELAY; POWER TRANSFORMERS; PROTECTION;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Percentage restrained differential protection is widely used as the main protection of bulk power transformers. For any differential current based transformer protection scheme, an important problem is to distinguish the magnetizing inrush from faults to prevent the possible mal-operation of differential relays. Traditionally, the second harmonic restraint principle is adopted as the standard method to maintain the security of relays during the inrush events. In recent years, the improvement of the magnetic characteristics of transformer iron core materials led to the relatively lower second harmonic components in magnetizing inrush currents; in contrast, higher second harmonic components in short circuit currents due to CT saturation and the effect of distributed capacitance of the EHV long line connected to the protected transformer have been observed, which makes the choosing of an appropriate harmonic restraint ratio more difficult. In this paper, a fast flux restraint algorithm used to identify the magnetizing inrush current is presented. Based on the sampled voltage/current values, the algorithm calculates the changing rate of magnetic fluxes in iron core to determine the saturation status of the protected transformer. The saturation status is traced by a group of counters. The counter threshold derived from testing is used to determine if the relay should be blocked. The proposed algorithm can be applied to all kinds of transformer iron core structures and its effectiveness can be verified through the test cases.
引用
收藏
页数:5
相关论文
共 50 条
  • [1] New algorithm for inrush current identification of transformer based on support vector machine
    Hao, Wenbin
    Li, Qunzhan
    Huang, Yongrong
    Han, Zhengqing
    Xinan Jiaotong Daxue Xuebao/Journal of Southwest Jiaotong University, 2007, 42 (04): : 490 - 493
  • [2] A new algorithm for avoiding maloperation of transformer restricted earth fault protection caused by the transformer magnetizing inrush current and current transformer saturation
    Krstivojevic, Jelisaveta
    Djuric, Milenko
    TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2016, 24 (06) : 5025 - 5042
  • [3] Study for Identification Algorithm of Inrush Based on Sine Degree Principle of Differential Current Waveforms in Non-saturation of Transformer
    Liang Zhi-jian
    Gu Bin
    Tan Jian-chen
    ICEET: 2009 INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT TECHNOLOGY, VOL 2, PROCEEDINGS, 2009, : 295 - 299
  • [4] Identification Method of Transformer Magnetizing Inrush Current Based on Comprehensive Morphological Algorithm
    Zhang Y.
    Gao H.
    Du S.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2021, 45 (24): : 165 - 173
  • [5] A new identification method of the transformer inrush current based on improved Hilbert-Huang transform algorithm
    Wu, Na
    Fan, Shuxian
    Liu, Lin
    Gao, Yan
    Wei, Aying
    DYNA, 2020, 95 (03): : 305 - 312
  • [6] A Method for Identification of Transformer Inrush Current Based on Box Dimension
    Gong, Maofa
    Zheng, Ran
    Hou, Linyuan
    Wei, Jingyu
    Wu, Na
    MATHEMATICAL PROBLEMS IN ENGINEERING, 2017, 2017
  • [7] Identification Method of Transformer Inrush Current Based on Skewness Coefficient
    Hu S.
    Jiang Y.
    Huang C.
    Jiang, Yaqun (yaqunjiang@21cn.com), 1954, Power System Technology Press (42): : 1954 - 1959
  • [8] A New Efficient Algorithm to Detect Current Transformer Saturation
    Kumar, Kanhaiya
    Kumbhar, Ganesh B.
    Mahajan, Satish
    2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM), 2016,
  • [9] Morphological identification of transformer magnetising inrush current
    Sun, P
    Zhang, JF
    Zhang, DJ
    Wu, QH
    Potts, S
    ELECTRONICS LETTERS, 2002, 38 (09) : 437 - 438
  • [10] Estimation of transformer saturation characteristics from inrush current waveforms
    Abdulsalam, Sami
    Xu, Wilsun
    Neves, W. L. A.
    Liu, Xian
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 2628 - 2628