Exposure of health care workers and occupants to coughed airborne pathogens in a double-bed hospital patient room with overhead mixing ventilation

被引:78
作者
Bolashikov, Zhecho D. [1 ]
Melikov, Arsen K. [1 ]
Kierat, Wojciech [2 ]
Popiolek, Zbigniew [2 ]
Brand, Marek [1 ]
机构
[1] Tech Univ Denmark, Dept Civil Engn, DK-2800 Lyngby, Denmark
[2] Silesian Tech Univ, Dept Heating Ventilat & Dust Removal Technol, Gliwice, Poland
来源
HVAC&R RESEARCH | 2012年 / 18卷 / 04期
关键词
PEAK VELOCITY TIME; EXPIRATORY AEROSOLS; THERMAL MANNEQUINS; FLOW-RATE; DISPERSION; TRANSPORT; ENVIRONMENT; INFECTION; RISK; FATE;
D O I
10.1080/10789669.2012.682692
中图分类号
O414.1 [热力学];
学科分类号
摘要
The exposure of a doctor and a second patient was studied in a simulated two-bed hospital isolation room. The room was ventilated at three air change rates (3 h(-1), 6 h(-1), and 12 h(-1)) by mixing air distribution keeping at 22 degrees C(71.6 degrees F). The effect of the distance between the doctor and the coughing person, the posture of the coughing patient (lying sideways facing the doctor or on back), and the position of the doctor (facing the coughing patient or standing sideways) was examined with respect to exposure to coughed air. A thermal manikin with realistic body shape and surface temperature distribution was used to resemble the doctor. A coughing patient (equipped with cough generator) lying in one bed and another patient in the second bed were simulated by two heated dummies with simplified geometry. The cough consisted of 100% CO2. The peak cough time was 4 s, when the doctor was closest to the sick patient's bed, and more than doubled for the exposed patient. The level of exposure (peak concentration level) depended strongly on the positioning and distance of the doctor from the infected patient and posture of the coughing patient. Peak concentration level varied widely from 194 to 10,228 ppm. Ventilation rates of 12 h(-1) (recommended by present hospital standards) resulted in background velocities exceeding 0.5 m/s (98.43 fpm), suggesting elevated risk from draught discomfort.
引用
收藏
页码:602 / 615
页数:14
相关论文
共 41 条
[1]  
AHRAE, 2004, 552004 ANSIAHRAE
[2]  
[Anonymous], 1998, 1752 CEN CR
[3]  
[Anonymous], 2005, ISODIS7730
[4]  
ASHRAE, 2008, 1702008 ASHRAEASHE
[5]  
ASHRAE, 2005, 1132005 ANSIASHRAE
[6]   The ventilation of multiple-bed hospital wards: Review and analysis [J].
Beggs, Clive B. ;
Kerr, Kevin G. ;
Noakes, Catherine J. ;
Hathway, E. Abigail ;
Sleigh, P. Andrew .
AMERICAN JOURNAL OF INFECTION CONTROL, 2008, 36 (04) :250-259
[7]  
CDC and HICPAC, 2003, GEN INF, P1
[8]   Development of ventilation design strategy for effective removal of pollutant in the isolation room of a hospital [J].
Cheong, K. W. D. ;
Phua, S. Y. .
BUILDING AND ENVIRONMENT, 2006, 41 (09) :1161-1170
[9]  
Decker J., 1995, Applied Occupational Environmental, Hygiene, V10, P887
[10]   Inhaling to mitigate exhaled bioaerosols [J].
Edwards, DA ;
Man, JC ;
Brand, P ;
Katstra, JP ;
Sommerer, K ;
Stone, HA ;
Nardell, E ;
Scheuch, G .
PROCEEDINGS OF THE NATIONAL ACADEMY OF SCIENCES OF THE UNITED STATES OF AMERICA, 2004, 101 (50) :17383-17388