Thermal comfort assessment of large-scale hospitals in tropical climates: A case study of University Kebangsaan Malaysia Medical Centre (UKMMC)

被引:66
作者
Azizpour, F. [1 ]
Moghimi, S. [1 ]
Salleh, E. [1 ]
Mat, S. [1 ]
Lim, C. H. [1 ]
Sopian, K. [1 ]
机构
[1] Univ Kebangsaan Malaysia, Solar Energy Res Inst, Bangi 43600, Malaysia
关键词
Thermal comfort; Predicted mean vote (PMV); Thermal sensation vote (TSV); Effective temperature (ET*); Operative temperature (OT); Neutral temperature; HUMID TROPICS; ENVIRONMENTS; PREFERENCES; ADAPTATION; STANDARDS;
D O I
10.1016/j.enbuild.2013.05.033
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A field study on thermal comfort assessment was carried out in a large-scale hospital in a tropical climate. To evaluate thermal comfort, both subjective and objective measurements were performed. The data were collected from 10 various thermal zones of a hospital. In each zone the predicted mean vote (PMV) was calculated based on the Fanger theory. In addition, the thermal sensation vote (TSV) was calculated according to the survey to find the relationship between the Fanger model (PMV) and the occupants' votes. In this study a strong relationship between PMV and TSV was found when R-2 = 0.88. According to this correlation the neutrality point shifted to +0.7 on the seven-point ASHRAE scale. Moreover, the neutral effective temperature (ET*) was calculated based on the TSV and PMV of 23.4 degrees C and 21.3 degrees C, respectively, indicative of compatibility with the adaptive theory. The results also demonstrate that the preferred effective temperature according to subjective assessment in this case study is 20.2 degrees C. This analysis revealed that to the respondents of this study in 10 thermal zones the neutral temperature point is higher than global standards, while the preferred temperature is lower than standards and the neutrality point. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:317 / 322
页数:6
相关论文
共 29 条
[1]  
[Anonymous], T AM SOC HEATING REF
[2]  
[Anonymous], 2005, Ergonomics of the thermal environment _ Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria
[3]  
ASHRAE, 2010, ANSI/ASHRAE Standard 55-2020
[4]  
Azizpour F., 2012, INDOOR BUILT ENV
[5]  
Azizpour F., 2011, P 5 WSEAS INT C REC, P207
[6]  
Azizpour F., 2011, 4 WSEAS INT C REC RE, P171
[7]  
Azizpour F., 2012, ADV ENV BIOTECHNOLOG, P157
[8]  
Bouden C., 2001, P C MOV THERM COMF S
[9]   Thermal adaptation in the built environment: a literature review [J].
Brager, GS ;
de Dear, RJ .
ENERGY AND BUILDINGS, 1998, 27 (01) :83-96
[10]   A TALE OF 2 POPULATIONS - THERMAL COMFORT IN AIR-CONDITIONED AND NATURALLY VENTILATED OFFICES IN THAILAND [J].
BUSCH, JF .
ENERGY AND BUILDINGS, 1992, 18 (3-4) :235-249