An Adaptive Controller for the Shunt Active Filter Considering a Dynamic Load and the Line Impedance

被引:32
作者
Valdez, A. A. [1 ]
Escobar, G. [2 ]
Ortega, R. [3 ]
机构
[1] ITESI, Lab Proc & Qual Energy, Irapuato 36821, Gto, Mexico
[2] ABB Switzerland Ltd, CH-4505 Baden 5, Datwill, Switzerland
[3] SUPELEC, CNRS, LSS, F-91192 Gif Sur Yvette, France
关键词
Active filters; adaptive estimation; power distribution; power system harmonics; reactive power control; CONTROL STRATEGY; POWER FILTERS; FRAME;
D O I
10.1109/TCST.2008.2000987
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This brief presents a controller for an active filter to compensate reactive power and current harmonic distortion in a single phase system, i.e., to guarantee a power factor close to unity. The proposed controller considers the deleterious effects caused by the interaction between load and line impedances, which may lead to instabilities when the controller is enabled. The rationale behind the solution consists in the introduction of a lead compensator with a gain that is adjusted by adaptation, which replaces the conventional proportional term. This modification improves the stability conditions when the load and source impedances are non-negligible. In particular, the scheme provides a solution in the critical scenario, when the load is composed by a capacitor connected in parallel to a distorted current source. Special attention is given to the current control loop because it is precisely in this loop where the instability problems are generated. Realistic numerical results are provided to illustrate the benefits of the proposed solution.
引用
收藏
页码:458 / 464
页数:7
相关论文
共 18 条
[1]   CONTROL STRATEGY OF ACTIVE POWER FILTERS USING MULTIPLE VOLTAGE-SOURCE PWM CONVERTERS [J].
AKAGI, H ;
NABAE, A ;
ATOH, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1986, 22 (03) :460-465
[2]   Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems [J].
Akagi, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :354-363
[3]   A shunt active filter based on voltage detection for harmonic termination of a radial power distribution line [J].
Akagi, H ;
Fujita, H ;
Wada, K .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (03) :638-645
[4]  
[Anonymous], 1986, Stability of Adaptive Systems
[5]   An adaptive controller in stationary reference frame for D-Statcom in unbalanced operation [J].
Escobar, G ;
Stankovic, AM ;
Mattavelli, P .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2004, 51 (02) :401-409
[6]   A single synchronous frame hybrid (SSFH) multifrequency controller for power active filters [J].
Etxeberria-Otadui, Ion ;
Lopez de Heredia, Amaia ;
Gaztanaga, Haizea ;
Bacha, Seddik ;
Reyero, Raul .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1640-1648
[7]   INTERNAL MODEL PRINCIPLE FOR LINEAR-MULTIVARIABLE REGULATORS [J].
FRANCIS, BA ;
WONHAM, WM .
APPLIED MATHEMATICS AND OPTIMIZATION, 1975, 2 (02) :170-194
[8]  
Kassakian J., 1991, Principles of Power Electron
[9]  
Khositkasame S, 1997, PROCEEDINGS OF THE POWER CONVERSION CONFERENCE - NAGAOKA 1997, VOLS I AND II, P181, DOI 10.1109/PCCON.1997.645608
[10]  
Magoarou L., 1994, P IEEE IND EL CONTR, V1, P416