Heat transfer enhancement during R-404A vapor condensation in swirling flow

被引:12
|
作者
Salimpour, M. R. [1 ]
Yarmohammadi, S. [1 ]
机构
[1] Isfahan Univ Technol, Dept Mech Engn, Esfahan 8415683111, Iran
关键词
Heat transfer; Condensation; Performance; R-404A; Turbulator; TWISTED TAPE INSERTS; PRESSURE-DROP; CONVECTIVE CONDENSATION; HORIZONTAL TUBE; AUGMENTATION;
D O I
10.1016/j.ijrefrig.2012.05.015
中图分类号
O414.1 [热力学];
学科分类号
摘要
In the present study, an experimental investigation has been performed to examine the heat transfer enhancement achieved by twisted tape inserts during forced convective condensation of R-404A vapor inside horizontal tubes. The test section was a coaxial double-pipe counter-flow heat exchanger where R-404A flowed in the inner tube and coolant water flowed through the annulus. Four full-length twisted tapes with twist ratios of 4, 7, 10 and 14 were used on the refrigerant side of test-condenser. Experiments were carried out for plain tube and twisted tape inserted tubes at five R-404A mass velocities for each tube. Investigation of the results showed that employing twisted tape inserts inside tube increases the average heat transfer coefficient up to approximately 50% above the plain tube values. Moreover, a performance evaluation for the twisted tape inserted tubes was accomplished. (C) 2012 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:2014 / 2021
页数:8
相关论文
共 50 条