Joint Optimization of Operation and Maintenance Policies for Solar-Powered Microgrids

被引:21
作者
Mahani, Khashayar [1 ]
Liang, Zhenglin [2 ]
Parlikad, Ajith Kumar [2 ]
Jafari, Mohsen A. [1 ]
机构
[1] Rutgers State Univ, Dept Ind & Syst Engn, Piscataway, NJ 08854 USA
[2] Univ Cambridge, Inst Mfg, Dept Engn, Cambridge CB3 0FS, England
基金
英国工程与自然科学研究理事会;
关键词
Two level optimization; operation dependence; condition-based maintenance; linear programming and continuous-time Markov chain; ENERGY-STORAGE; RELIABILITY; SYSTEMS; FRAMEWORK;
D O I
10.1109/TSTE.2018.2849318
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In a solar-powered microgrid (MG), the optimal maintenance strategy is influenced by the downtime cost of the photovoltaic (PV) system, which in turn depends on the operation PV within the MG network. Also, the dispatch policy used in the MG will influence the economic feasibility of maintenance plans. In this paper, we present an approach for optimizing the operation and maintenance policy jointly for a solar-powered MG considering the dependence between the two policies. The two-layered approach presented in this paper seeks to unify the practicality of simulation and the efficiency of analytical models. In the upper layer, we optimize the operation of MG by solving the optimal power dispatch within the MG network using linear programming approach. Then, we calculate the penalty costs under the aging conditions of PV systems. In the bottom layer, by incorporating the penalty costs as input parameters, we use a continuous-time Markov chain model to calculate the optimal maintenance policy for the PV system. The proposed approach could be used in the stipulation process between MG owner and PV system maintenance provider to minimize the money waste on both sides.
引用
收藏
页码:833 / 842
页数:10
相关论文
共 19 条
[1]   Stochastic Framework for Partially Degradation Systems with Continuous Component Degradation-Rate-Interactions [J].
Bian, Linkan ;
Gebraeel, Nagi .
NAVAL RESEARCH LOGISTICS, 2014, 61 (04) :286-303
[2]   A Simple Optimal Power Flow Model with Energy Storage [J].
Chandy, K. Mani ;
Low, Steven H. ;
Topcu, Ufuk ;
Xu, Huan .
49TH IEEE CONFERENCE ON DECISION AND CONTROL (CDC), 2010, :1051-1057
[3]  
Chen DY, 2002, RELIAB ENG SYST SAFE, V76, P43, DOI 10.1016/S0951-8320(01)00141-7
[4]   Sizing of Energy Storage for Microgrids [J].
Chen, S. X. ;
Gooi, H. B. ;
Wang, M. Q. .
IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (01) :142-151
[5]   Estimation of Photovoltaic System Reliability and Performance Metrics [J].
Dhople, Sairaj V. ;
Dominguez-Garcia, Alejandro D. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (01) :554-563
[6]  
Harsha P, 2011, IEEE DECIS CONTR P, P5813
[7]   Intelligent Dispatch for Distributed Renewable Resources [J].
Hopkins, Mark D. ;
Pahwa, Anil ;
Easton, Todd .
IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (02) :1047-1054
[8]  
Jacobi J., 2010, Solar Photovoltaic Plant Operation and Maintenance costs
[9]   Assessment of the safe operation and maintenance of photovoltaic systems [J].
Kamenopoulos, Sotiris N. ;
Tsoutsos, Theocharis .
ENERGY, 2015, 93 :1633-1638
[10]  
Kanoria Yashodhan, 2011, 2011 49th Annual Allerton Conference on Communication, Control, and Computing (Allerton), P1310