Filter Design Masks for C37.118.1a-Compliant Frequency-Tracking and Fixed-Filter M-Class Phasor Measurement Units

被引:22
作者
Roscoe, Andrew J. [1 ]
Dickerson, Bill [2 ]
Martin, Kenneth E. [3 ]
机构
[1] Univ Strathclyde, Dept Elect & Elect Engn, Glasgow G1 1XW, Lanark, Scotland
[2] Arbiter Syst Inc, Paso Robles, CA 93446 USA
[3] Elect Power Grp, Pasadena, CA 91101 USA
关键词
Fourier transforms; frequency measurement; phase estimation; power system measurements; power system parameter estimation; power system state estimation; SYNCHROPHASOR ESTIMATION;
D O I
10.1109/TIM.2015.2445111
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The new amendment to the phasor measurement unit (PMU) standard C37.118.1a makes several significant changes compared with the standard C37.118.1 (2011). This paper highlights some of the most important changes, with a particular emphasis applied to how those changes relate to the way that an M-class PMU filter needs to be designed. In particular, there is a delicate tradeoff between passband flatness (the bandwidth test) and stopband rejection in the out-of-band (OOB) test. For a PMU algorithm using frequency-tracking and adaptive filters, it is shown that passband flatness can be relaxed to about 2.5 dB, but that the stopband needs to begin up to 14.8% closer to 0 Hz than for a fixed-filter PMU. This is partly due to the exact procedures of the C37.118.1a OOB testing and partly due to the adaptive nature of a frequency-tracking PMU filter section. Both the above lead to modified filter masks being required for frequency-tracking devices compared with the mask required for fixed-filter devices. The M-class PMU with a reporting rate of 25 Hz is the most difficult to design, for reasons given in this paper. The validity of the masks is shown using filter Bode plots and simulated C37.118.1a test results of a fixed-filter and frequency-tracking device, which have been designed to meet the masks defined in this paper.
引用
收藏
页码:2096 / 2107
页数:12
相关论文
共 21 条
[1]   Dynamic Harmonic Analysis Through Taylor-Fourier Transform [J].
Angel Platas-Garza, Miguel ;
Antonio de la O Serna, Jose .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2011, 60 (03) :804-813
[2]  
[Anonymous], 2014, IEEE SYNCHR MEAS TES, DOI [10.1109/IEEESTD.2014.6983521, DOI 10.1109/IEEESTD.2014.6983521]
[3]  
[Anonymous], 2015, IEEE Std, VC37, P245
[4]  
[Anonymous], 2014, C371181A2014 IEEE
[5]  
Arbiter Systems, 2012, MOD 1133A PHAS MEAS
[6]  
Belega D, 2013, IEEE IMTC P, P946
[7]   Accuracy Analysis of the Multicycle Synchrophasor Estimator Provided by the Interpolated DFT Algorithm [J].
Belega, Daniel ;
Petri, Dario .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2013, 62 (05) :942-953
[8]  
Bertolim M., 2014, P IEEE INT WORKSH AP, P1
[9]   A Fast and Accurate PMU Algorithm for P plus M Class Measurement of Synchrophasor and Frequency [J].
Castello, Paolo ;
Liu, Junqi ;
Muscas, Carlo ;
Pegoraro, Paolo Attilio ;
Ponci, Ferdinanda ;
Monti, Antonello .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2014, 63 (12) :2837-2845
[10]  
Castello P, 2012, IEEE IMTC P, P294