Energy Audit of a 400/220 kV Substation - a Case Study

被引:0
作者
Jaralikar, Sunil M. [1 ]
Aruna, Mangalpady [2 ]
机构
[1] Govt Polytech Bicholim, Dept Elect Engn, Bicholim, Goa, India
[2] Natl Inst Technol, Min Engn Dept, Mangalore, India
来源
2011 INTERNATIONAL CONFERENCE AND UTILITY EXHIBITION ON POWER AND ENERGY SYSTEMS: ISSUES & PROSPECTS FOR ASIA (ICUE) | 2011年
关键词
Bus reactor; Energy audit; Extra High Voltage (EHV) substation; Performance analysis; Station efficiency; Transformer efficiency; Power quality; Technical and commercial viability;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The paper highlights the necessity of undertaking performance analysis and energy audit study of an electrical installation, more particularly a power substation on regular basis. A 630 MVA, 400/220 kV substation was identified and a detailed study was carried out to assess the various station performance parameters under different operating conditions. It was observed that the installed capacity of the station (transformer) was very large compared to the actual load it had to supply. Thus the station was under loaded and underutilized for the major period of its operation. This reduced the operational efficiency of the station. Secondly the incoming line voltage level was remaining high during most of the period of operation. Presently voltage is tried to be maintained by switching ON the line reactors at the receiving and sending ends of this station, switching OFF one of the 400 kV incoming lines during off peak loading conditions, thus risking the supply reliability. The present study emphasizes on the urgent need for improving the power quality, streamlining and optimizing the station capacity, operations and its loading pattern. Accordingly suggestions are proposed for the same.
引用
收藏
页数:8
相关论文
共 12 条
[1]  
[Anonymous], P 2004 POW SYST ICPS, P131
[2]  
Beggs Clive, 2002, ENERGY MANAGEMENT CO, P73
[3]  
Bureau of Energy Efficiency, 2005, EN PERF ASS D EQ UT
[4]  
Bureau of Energy Efficiency, 2005, GEN ASP EN MAN EN AU
[5]  
Cauret Lionel, 2001, EUROPEAN ENERGY IND
[6]  
Gupta C. P., P 2004 POW SYST ICPS, P137
[7]  
Hamlin Lawrence D., 1990, ELECT J, V3, P30
[8]   RENEWABLE SOURCES OF ENERGY AND THE ENVIRONMENT - ELHINNAWI,E, BISWAS,AK [J].
MACKILLOP, A .
ENERGY POLICY, 1982, 10 (04) :370-370
[9]   THERMAL-RESISTANCE BEHAVIOR OF SINGLE AND MULTIPLE LAYERS OF CLOTHING FABRICS UNDER MECHANICAL LOAD [J].
OCALLAGHAN, PW ;
PROBERT, SD .
APPLIED ENERGY, 1977, 3 (01) :3-12
[10]  
Parida Sanjoy, P 2004, P705