Behavior of induction motor due to voltage sags and short interruptions

被引:49
作者
Gomez, JC [1 ]
Morcos, MM
Reineri, CA
Campetelli, GN
机构
[1] Rio Cuarto Natl Univ, Elect Power Syst Protect Inst, Cordoba, Argentina
[2] Kansas State Univ, Dept Elect & Comp Engn, Manhattan, KS 66506 USA
基金
日本科学技术振兴机构;
关键词
hot-load pickup; induction motor; motor reacceleration; power quality; short interruptions; voltage sags;
D O I
10.1109/61.997914
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An experimental study and some calculations on induction motor behavior were carried out. The effects due to short interruptions and voltage sags were investigated. A standard three-phase squirrel-cage motor of 5.5 kW, 1500 r/min, and 380 V was used. The presence of induction motor changes the voltage sag waveform and duration. Protection characteristic curves and contactor ride-through capability together with their improvement are also studied. The interaction between motor load, system hot-load pickup, and voltage sag magnitude determine the motor re-acceleration duration and magnitudes. Besides, on-sag and post-sag currents can reach levels higher than the direct start values. Post-sag overcurrent duration can last more than twice the normal start time period, having specific energies in the same order of magnitude.
引用
收藏
页码:434 / 440
页数:7
相关论文
共 13 条
[1]   THE INFLUENCE OF MOTOR REACCELERATION ON VOLTAGE SAGS [J].
BOLLEN, MHJ .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1995, 31 (04) :667-674
[2]  
COLLINS ER, 1997, P IEEE ANN TEXT FIB
[3]   EFFECTS OF MOMENTARY VOLTAGE DIPS ON THE OPERATION OF INDUCTION AND SYNCHRONOUS MOTORS [J].
DAS, JC .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1990, 26 (04) :711-718
[4]   Interpreting recent power quality surveys to define the electrical environment [J].
Dorr, DS ;
Hughes, MB ;
Gruzs, TM ;
Jurewicz, RE ;
McClain, JL .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (06) :1480-1487
[5]  
Gomez J. C., 2001, IEEE Power Engineering Review, V21, P11, DOI 10.1109/39.896812
[6]   Transient motor reacceleration study in an integrated petrochemical facility [J].
Grewal, GS ;
Pocsai, S ;
Hakim, MM .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (04) :968-977
[7]   A SURVEY OF DISTRIBUTION-SYSTEM POWER QUALITY - PRELIMINARY-RESULTS [J].
GUNTHER, EW ;
MEHTA, H ;
SAVAGE, N .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (01) :322-329
[8]  
HEYDT GT, 1991, ELECT POWER QUALITY
[9]  
Key T. S., 1995, IEEE Industry Applications Magazine, V1, P6, DOI 10.1109/2943.378057
[10]   Effects of unbalanced voltage on the operation performance of a three-phase induction motor [J].
Lee, CY .