Performance investigation of a two-phase transcritical CO2 ejector heat pump system

被引:32
作者
Taleghani, S. Taslimi [1 ]
Sorin, M. [1 ]
Poncet, S. [1 ]
Nesreddine, H. [2 ]
机构
[1] Univ Sherbrooke, Mech Engn Dept, Sherbrooke, PQ J1K 2R1, Canada
[2] Hydroquebec, 600 Rue Montagne, Shawinigan, PQ G9N 7N5, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Two-phase ejector; CO2 transcritical cycle; Heat pump; Heat transfer area; Parametric analysis; Thermodynamic simulation; REFRIGERATION CYCLE; GEOMETRY EJECTORS; PRESSURE-DROP; OPTIMIZATION; DESIGN; EFFICIENCIES; DIMENSIONS;
D O I
10.1016/j.enconman.2019.02.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study of the thermodynamic performance of a transcritical CO2 ejector heat pump cycle presents a numerical analysis under the constraint of constant total heat transfer area. An experimentally validated model of a CO2 heat pump system and a model of a two-phase ejector are combined to perform the study. The effects of chosen parameters on system performance are investigated: operating conditions as determined by the gas cooler and evaporator pressures; ejector design parameters including the primary throat diameter, effective area ratio, and diffuser outlet diameter; system design as defined by the heat transfer area ratio. The results of this analysis allow specifying the optimal range for the design parameters in order to maximize the COP and the heating capacity of the heat pump. The heat transfer area ratio is shown to have important effects on the COP and heating capacity as well as the optimal gas cooler pressure. As the heat transfer area ratio increases, COP and heating capacity increase as well, while the optimum gas cooler pressure decreases. At given ejector geometries and operating conditions, this optimization can increase the COP and heating capacity of the ejector heat pump by approximately 17% and 20% respectively by increasing the heat transfer area ratio.
引用
收藏
页码:442 / 454
页数:13
相关论文
共 53 条
  • [1] Transcritical carbon dioxide heat pump systems: A review
    Austin, Brian T.
    Sumathy, K.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2011, 15 (08) : 4013 - 4029
  • [2] Plate heat exchanger literature survey and new heat transfer and pressure drop correlations for refrigerant evaporators
    Ayub, ZH
    [J]. HEAT TRANSFER ENGINEERING, 2003, 24 (05) : 3 - 16
  • [3] Development and performance mapping of a multi-ejector expansion work recovery pack for R744 vapour compression units
    Banasiak, Krzysztof
    Hafner, Armin
    Kriezi, Ekaterini E.
    Madsen, Kenneth B.
    Birkelund, Michael
    Fredslund, Kristian
    Olsson, Rickard
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 57 : 265 - 276
  • [4] Experimental and numerical investigation of the influence of the two-phase ejector geometry on the performance of the R744 heat pump
    Banasiak, Krzysztof
    Hafner, Armin
    Andresen, Trond
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (06): : 1617 - 1625
  • [5] 1D Computational model of a two-phase R744 ejector for expansion work recovery
    Banasiak, Krzysztof
    Hafner, Armin
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (11) : 2235 - 2247
  • [6] Ejector refrigeration: A comprehensive review
    Besagni, Giorgio
    Mereu, Riccardo
    Inzoli, Fabio
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 53 : 373 - 407
  • [7] A novel transcritical CO2 refrigeration cycle with two ejectors
    Cen, Jiwen
    Liu, Pei
    Jiang, Fangming
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (08): : 2233 - 2239
  • [8] Experimental investigation of an adjustable ejector for CO2 heat pump water heaters
    Chen, Guang-ming
    Liang, Li-xia
    Tang, Li-ming
    Xu, Xiao-xiao
    Zhu, Zhi-jiang
    Chen, Qi
    [J]. JOURNAL OF ZHEJIANG UNIVERSITY-SCIENCE A, 2009, 10 (11): : 1678 - 1682
  • [9] Optimum design of ejector refrigeration systems with environmentally benign fluids
    Dahmani, Abdelouahid
    Aidoun, Zine
    Galanis, Nicolas
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (08) : 1562 - 1572
  • [10] Danilova GN, 1981, KHOLOD TEK, V4, P25