Experimental research on the water mist fire suppression performance in an enclosed space by changing the characteristics of nozzles

被引:50
|
作者
Liu Yinshui [1 ]
Jiang Zhuo [1 ]
Wang Dan [1 ]
Li Xiaohui [1 ]
机构
[1] Huazhong Univ Sci & Technol, Res Ctr Hydraul & Pneumat Technol, Sch Mech Sci & Engn, Wuhan 430074, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
Water mist; Fire suppression performance; Pressure-swirl nozzles; Spray cone angle; Flow rate; LIQUID POOL FIRES; EXTINGUISHMENT; SYSTEM;
D O I
10.1016/j.expthermflusci.2013.09.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
Water mist is an ideal way in enclosed spaces, where fire suppression efficiency is very important due to limited water and water damage to equipment. The purpose of this paper is to find a more effective way of fire suppression performance by changing characteristics of nozzles, taking into account extinguishing time, water consumption, toxic gas concentration, temperature decay and cover area. Two groups of pressure-swirl nozzles with the same flow rate and different spray cone angles were employed. The angle was adjusted by changing diameters and lengths of entrance, swirl chamber and orifice of nozzle. It was found that the cover area and the droplet size increased slightly with the spray angle. The fire tests results showed that the extinguishing time increased with the spray cone angle, and increased with the flow rate and the operating pressure decreasing. The temperature decay rate was improved by decreasing the angle or increasing the flow rate. In addition, with an increase in the extinguishing time, the concentration of O-2 decreased while the CO and CO2 increased. However, the gas concentrations were not affected by the water mist discharge duration if it exceeded the extinguishing time. For a specific region and a certain amount of water, the performance can be improved by the approach: increasing the flow rate and the spray angle simultaneously and decreasing the discharge duration. The authors suggest setting proper flow rate and spray cone angle which match mutually, in order to maximize the utilization of water. (C) 2013 Elsevier Inc. All rights reserved.
引用
收藏
页码:174 / 181
页数:8
相关论文
共 50 条
  • [1] Effectiveness of Swirl Water Mist Nozzles for Fire Suppression
    Kraus-Namrozy, Natalia
    Brzezinska, Dorota
    INTERNATIONAL JOURNAL OF ENVIRONMENTAL RESEARCH AND PUBLIC HEALTH, 2022, 19 (23)
  • [2] Experimental study on the pulse water mist fire suppression system performance in a confined space
    P. Y. Lun
    Q. Zhang
    X. K. Li
    Journal of the Brazilian Society of Mechanical Sciences and Engineering, 2020, 42
  • [3] Experimental study on the pulse water mist fire suppression system performance in a confined space
    Lun, P. Y.
    Zhang, Q.
    Li, X. K.
    JOURNAL OF THE BRAZILIAN SOCIETY OF MECHANICAL SCIENCES AND ENGINEERING, 2020, 42 (05)
  • [4] Experimental Study on Characteristics of Water Mist Fire Suppression for Cooking Fume
    Xie, Zhengwen
    Jiang, Zhengpei
    2015 4TH INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENTAL PROTECTION (ICEEP 2015), 2015, : 596 - 601
  • [5] An experimental study of the effects of water mist characteristics on pool fire suppression
    Gupta, Meenakshi
    Pasi, Amit
    Ray, Anjan
    Kale, S. R.
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2013, 44 : 768 - 778
  • [6] Experimental and Numerical Study of Fire Suppression Performance of Ultral-Fine Water Mist in a Confined Space
    Liang Tian-shui
    Liu Zhong-lin
    Xiao Xiu-kun
    Luo Siu-ming
    Liao Guang-xuan
    Zhong Wei
    2012 INTERNATIONAL CONFERENCE ON PERFORMANCE-BASED FIRE AND FIRE PROTECTION ENGINEERING, 2013, 52 : 208 - 213
  • [7] Experimental evaluation of fire suppression characteristics of twin fluid water mist system
    Gupta, Meenakshi
    Rajora, R.
    Sahai, S.
    Shankar, R.
    Ray, Anjan
    Kale, S. R.
    FIRE SAFETY JOURNAL, 2012, 54 : 130 - 142
  • [8] Fire suppression performance of water mist systems with additives
    Kim, AK
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL II, PT A AND B, 2000, 2 : 561 - 566
  • [9] Influence of additives on the fire suppression performance of water mist
    Jiang, Juncheng, 1600, China University of Mining and Technology (43):
  • [10] Research on atomization characteristics of high-pressure water mist atomizer for fire suppression
    Fan, Minghao
    Zhou, Hua
    Yang, Huayong
    Jixie Gongcheng Xuebao/Chinese Journal of Mechanical Engineering, 2002, 38 (09): : 17 - 21