A New Multiconductor Cell Three-Dimension Matrix-Based Analysis Applied to a Three-Core Armoured Cable

被引:37
作者
Benato, Roberto [1 ]
Sessa, Sebastian Dambone [1 ]
机构
[1] Padova Univ, Dept Ind Engn, I-3513 Padua, Italy
关键词
Three-core armoured cables; lay length; multiconductor cell analysis; eddy currents; power losses; MAGNETIC-FIELD; POWER-CABLES; WIND FARMS; LINE; BEHAVIOR; MODEL;
D O I
10.1109/TPWRD.2017.2757084
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a procedure based on three-dimension matrices is presented: it is the generalization of multiconductor cell analysis to any transmission line where the positions of all the active and passive conductors may change with continuity along their length. A meaningful example of this is given by a three-core single lead-screened armoured cable where cores and armour wires are wound helically with different lay lengths. Therefore, this generalization is presented with reference to these cables but it can be applied to any transmission line. The proposed matrix procedures can be implemented in any standard computer by means of a mathematical software (e.g., MATLAB). The computational complexity of this novel method is shown in comparison with the finite element method commercial software FLUX 3D, which takes 70 h for meshing and solving a 3-m long model. On the contrary, the present matrix algorithms take from minute fractions to maximum 2 min (depending on subconductor number) to obtain results having negligible differences with respect to FEM FLUX 3D ones if paramagnetic materials are involved and differences up to maximum 7% with ferromagnetic ones (which imply, for submarine cable installations, a current rating computation difference lower than 3%).
引用
收藏
页码:1636 / 1646
页数:11
相关论文
共 34 条
[1]  
[Anonymous], 2017, P 2017 EVOLVING ADAP
[2]   Stochastic Optimization Model for Electric Power System Planning of Offshore Wind Farms [J].
Banzo, Marcos ;
Ramos, Andres .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2011, 26 (03) :1338-1348
[3]   Proximity effect and magnetic field calculation in GIL and in isolated phase bus ducts [J].
Benato, R ;
Dughiero, F ;
Forzan, M ;
Paolucci, A .
IEEE TRANSACTIONS ON MAGNETICS, 2002, 38 (02) :781-784
[4]   Distribution line carrier: Analysis procedure and applications to DG [J].
Benato, Roberto ;
Caldon, Roberto .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) :575-583
[5]   High-capability applications of long gas-insulated lines in structures [J].
Benato, Roberto ;
Di Mario, Claudio ;
Koch, Hermann .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) :619-626
[6]   Core laying pitch-long 3D finite element model of an AC three-core armoured submarine cable with a length of 3 metres [J].
Benato, Roberto ;
Sessa, Sebastian Dambone ;
Forzan, Michele ;
Marelli, Marco ;
Pietribiasi, Davide .
ELECTRIC POWER SYSTEMS RESEARCH, 2017, 150 :137-143
[7]   Review of high current rating insulated cable solutions [J].
Benato, Roberto ;
Colla, Luigi ;
Sessa, Sebastian Dambone ;
Marelli, Marco .
ELECTRIC POWER SYSTEMS RESEARCH, 2016, 133 :36-41
[8]   Zero sequence behaviour of a double-circuit overhead line [J].
Benato, Roberto ;
Sessa, Sebastian Dambone ;
Guglielmi, Fabio ;
Partal, Ertugrul ;
Tleis, Nasser .
ELECTRIC POWER SYSTEMS RESEARCH, 2014, 116 :419-426
[9]   Determination of Steady-State and Faulty Regimes of Overhead Lines by Means of Multiconductor Cell Analysis (MCA) [J].
Benato, Roberto ;
Sessa, Sebastian Dambone ;
Guglielmi, Fabio .
ENERGIES, 2012, 5 (08) :2771-2793
[10]   Multiconductor cell analysis of skin effect in Milliken type cables [J].
Benato, Roberto ;
Paolucci, Antonio .
ELECTRIC POWER SYSTEMS RESEARCH, 2012, 90 :99-106