Various studies and arrangements have been made in recent years to reduce the effect of refrigerants used in cooling and heating systems on climate change. Environmentally friendly refrigerants with low global warming potential are required to reduce the negative impact of air-conditioning systems on climate change. HFO and HFC/HFO refrigerant mixtures (such as R513A) are thought to replace HFC refrigerants and are also commercially produced recently. In this study, R134a, R1234yf and R513A refrigerants have been investigated theoretically and experimentally under the same operating conditions. Refrigerants were tested at the same evaporator (- 10 degrees C, - 5 degrees C and 0 degrees C) and condenser (35 degrees C) temperatures. In addition, life cycle climate performance assessment analyses of refrigerants were performed. It is found that when the evaporator temperature is - 10 degrees C and - 5 degrees C, R513A has a higher COP(HP)than R134a. However, R513A has a lower COP(HP)than R134a at 0 degrees C the evaporator temperature. R1234yf has a high COP(HP)compared to R134a at the - 10 degrees C evaporator temperature while it has a low COP(HP)at - 5 degrees C and 0 degrees C evaporator temperatures. R513A and R1234yf refrigerants have 14.45% and 17.16% less emissions than R134a, respectively.
引用
收藏
页码:1201 / 1210
页数:10
相关论文
共 24 条
[1]   HFOs and their binary mixtures with HFC134a working as drop-in refrigerant in a household refrigerator: Energy analysis and environmental impact assessment [J].
Aprea, C. ;
Greco, A. ;
Maiorino, A. .
APPLIED THERMAL ENGINEERING, 2018, 141 :226-233
[2]   An experimental investigation of the energetic performances of HFO1234yf and its binary mixtures with HFC134a in a household refrigerator [J].
Aprea, C. ;
Greco, A. ;
Maiorino, A. .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2017, 76 :109-117
[3]   Assessing the Environmental Sustainability of Electricity Generation in Turkey on a Life Cycle Basis [J].
Atilgan, Burcin ;
Azapagic, Adisa .
ENERGIES, 2016, 9 (01)
[4]   Energetic and Exergetic Analysis of Low Global Warming Potential Refrigerants as Substitutes for R410A in Ground Source Heat Pumps [J].
Bobbo, Sergio ;
Fedele, Laura ;
Curcio, Marco ;
Bet, Anna ;
De Carli, Michele ;
Emmi, Giuseppe ;
Poletto, Fabio ;
Tarabotti, Andrea ;
Mendrinos, Dimitris ;
Mezzasalma, Giulia ;
Bernardi, Adriana .
ENERGIES, 2019, 12 (18)
[5]   Life cycle climate performance evaluation (LCCP) on cooling and heating systems in South Korea [J].
Choi, Seyoung ;
Oh, Jinwoo ;
Hwang, Yunho ;
Lee, Hoseong .
APPLIED THERMAL ENGINEERING, 2017, 120 :88-98
[6]   ROLE OF REFRIGERANT MIXTURES AS ALTERNATIVES TO CFCS [J].
DIDION, DA ;
BIVENS, DB .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1990, 13 (03) :163-175
[7]   Experimental study on the influence of the flame retardants on the flammability of R1234yf [J].
Feng, Biao ;
Yang, Zhao ;
Zhai, Rui .
ENERGY, 2018, 143 :212-218
[8]  
HOGBERG M, 1994, INT J REFRIG, V17, P417
[9]  
IIR (International Institute of Refrigeration), 2016, Guideline for Life Cycle Climate Performance
[10]   Performance of virtually non-flammable azeotropic HFO1234yf/HFC134a mixture for HFC134a applications [J].
Lee, Yohan ;
Kang, Dong-gyu ;
Jung, Dongsoo .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (04) :1203-1207