Border-flow control by means of Phase Shifting Transformers

被引:10
作者
Verboomen, J. [1 ]
Van Hertem, D. [2 ]
Schavemaker, P. H. [1 ]
Kling, W. L. [1 ]
Belmans, R. [2 ]
机构
[1] Delft Univ Technol, Elect Power Syst Grp, Mekelweg 4, NL-2628 CD Delft, Netherlands
[2] ELECTA Res Grp, Heverlee, Belgium
来源
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5 | 2007年
关键词
Phase Shifting Transformer; load flow control; Linear Least Squares;
D O I
10.1109/PCT.2007.4538510
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, a control scheme is demonstrated that regulates multiple Phase Shifting Transformers (PSTs) to equally load the interconnectors of a border. A crucial step in the development of the control scheme is the derivation of Phase Shifter Distribution Factors (PSDFs), which indicate the influence of a PST on the active power flow on a certain line. Based on these PSDFs, the Linear Least Squares (LLS) method is used to calculate the optimal PST settings. The degree to which an even repartition can be obtained, depends on the number of PSTs in relation to the number of interconnectors. As a case-study, simulations are performed involving the Dutch and Belgian interconnectors.
引用
收藏
页码:1338 / +
页数:2
相关论文
共 8 条
[1]  
Gill P. E., 1981, PRACTICAL OPTIMIZATI
[2]   PHASE-SHIFTER AND POWER FLOW-CONTROL [J].
HAN, ZX .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (10) :3790-3795
[3]  
*IEEE POW ENG SOC, 2002, C57135 IEEE POW ENG
[4]  
Ilic M., 2000, DYNAMICS CONTROL LAR
[5]  
KLING WL, 2004, CIGRE SESSION 2004 C
[6]  
SPOORENBERG CJG, 2003, 13 INT S HIGH VOLT E
[7]  
VANHERTEM D, 2006, IEE INT C AC DC POW
[8]  
VERBOOMEN J, 2007, EUROPEAN T IN PRESS