Optimization of night ventilation performance in office buildings in a cold climate

被引:24
|
作者
Guo, Rui [1 ]
Heiselberg, Per [1 ]
Hu, Yue [1 ]
Zhang, Chen [1 ]
Vasilevskis, Sandijs [1 ]
机构
[1] Aalborg Univ, Dept Built Environm, Thomas Manns Vej 23, DK-9220 Aalborg, Denmark
关键词
Night ventilation performance; Global sensitivity analysis; Evolutionary optimization; PHASE-CHANGE MATERIALS; ENERGY-STORAGE; THERMAL MASS; PREDICTIVE CONTROL; COOLING-ENERGY; STRATEGIES; SYSTEM; HOT; PCM; REDUCTION;
D O I
10.1016/j.enbuild.2020.110319
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The rising cooling demand and overheating in the building sector, especially in office buildings, have intensified research interest in recent years. Night ventilation (NV) as a passive energy technology has shown a great potential cooling energy and ameliorate indoor thermal environment. In this paper, a holistic approach involving global sensitivity analysis and evolutionary optimization is developed to exclude insignificant parameters and explore optimal NV performance in terms of energy use and thermal comfort. The proposed approach is based on the simulation research of a three-story office building equipped with daytime air conditioning and NV system in a cold climate region. The NV system is equipped with three levels of specific fan power (SFP), representing cases with natural NV and medium and high SFP mechanical NV, respectively. The results show that the activation threshold temperature is not the key parameter for NV performance. Comparing with the case without NV, the three SFP NV systems under a general scheme save 8.8% to 82.5% total cooling energy consumption (TCEC), but increase the average percentage of dissatisfied during occupied hours (aPPD) from 7.5% to about 15%, which may cause overcooling penalty. The optimization decreases the thermal mass area and the night air change rate setpoint at each hour, while increases the minimum indoor air temperature setpoint compared to the general scheme. All three optimal NV schemes significantly improve the indoor thermal comfort by maintaining the aPPD at 7.5%. The optimal medium and high SFP mechanical NV scheme further save 7.1% and 38.6% TCEC compared to the corresponding general mechanical NV scheme, respectively. With a higher SFP, a greater energy saving potential is contributed through NV optimization process. Even though the optimal natural NV scheme consumes more than twice as much TCEC as the general natural NV scheme, it is still worth optimizing the natural NV since the indoor thermal comfort can be improved and the optimal scheme still saves much cooling energy compared to the base case. (C) 2020 Elsevier B.V. All rights reserved.
引用
收藏
页数:13
相关论文
共 50 条
  • [1] Climate adaptive optimization of green roofs and natural night ventilation for lifespan energy performance improvement in office buildings
    Shi, Dachuan
    Gao, Yafeng
    Zeng, Peng
    Li, Baizhan
    Shen, Pengyuan
    Zhuang, Chaoqun
    BUILDING AND ENVIRONMENT, 2022, 223
  • [2] On the Performance of Night Ventilation in a Historic Office Building in Nordic Climate
    Bakhtiari, Hossein
    Akander, Jan
    Cehlin, Mathias
    Hayati, Abolfazl
    ENERGIES, 2020, 13 (16)
  • [3] Night ventilation control strategies in office buildings
    Wang, Zhaojun
    Yi, Lingli
    Gao, Fusheng
    SOLAR ENERGY, 2009, 83 (10) : 1902 - 1913
  • [4] Simulation and optimization of night cooling with diffuse ceiling ventilation and mixing ventilation in a cold climate
    Guo, Rui
    Hu, Yue
    Heiselberg, Per
    Johra, Hicham
    Zhang, Chen
    Peng, Pei
    RENEWABLE ENERGY, 2021, 179 : 488 - 501
  • [5] Optimization of cool roof and night ventilation in office buildings: A case study in Xiamen, China
    Guo, Rui
    Gao, Yafeng
    Zhuang, Chaoqun
    Heiselberg, Per
    Levinson, Ronnen
    Zhao, Xia
    Shi, Dachuan
    RENEWABLE ENERGY, 2020, 147 : 2279 - 2294
  • [6] Influence of design parameters on the night ventilation performance in office buildings based on sensitivity analysis
    Guo, Rui
    Hu, Yue
    Liu, Mingzhe
    Heiselberg, Per
    SUSTAINABLE CITIES AND SOCIETY, 2019, 50
  • [7] Summer cooling for office-type buildings by night ventilation
    Kolokotroni, M
    Webb, BC
    Hayes, SD
    17TH AIVC CONFERENCE - OPTIMUM VENTILATION AND AIR FLOW CONTROL IN BUILDING, PROCEEDINGS, VOLS 1 AND 2, 1996, : 591 - 599
  • [8] Night cooling and ventilation design for office-type buildings
    Birtles, AB
    Kolokotroni, M
    Perera, MDAES
    RENEWABLE ENERGY, 1996, 8 (1-4) : 259 - 263
  • [9] Summer cooling with night ventilation for office buildings in moderate climates
    Kolokotroni, M
    Webb, BC
    Hayes, SD
    ENERGY AND BUILDINGS, 1998, 27 (03) : 231 - 237
  • [10] Night cooling and ventilation design for office-type buildings
    Building Research Establishment, Watford, United Kingdom
    Renewable Energ, 1 -4 pt 1 (259-263):