Effect of HVDC converter station faults on turbine-generator shaft torsional torques

被引:19
作者
Faried, SO
ElSerafi, AM
机构
[1] Power Systems Research Group, University of Saskatchewan, Saskatoon, Sask.
关键词
D O I
10.1109/59.589740
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper explores the impact of HVDC converter station faults on the torsional torques induced in turbine-generator shafts. In this context, investigations have been conducted on a large turbine-generator unit connected to an HVDC system. Faults considered are firethrough, misfire and a short-circuit across a non-conducting valve. The effect of the fault incidence time on the maximum turbine-generator torsional torques is also investigated. The results of these investigations are presented in the form of typical time responses as well as parametric studies.
引用
收藏
页码:875 / 881
页数:7
相关论文
共 20 条
[1]  
ABOLINS A, 1976, IEEE T POWER APPARAT, P14
[2]  
[Anonymous], 1983, HIGH VOLTAGE DIRECT
[3]  
[Anonymous], IEEE T POWER APPARAT
[4]  
ANWAHNA, 1987, IEEE T POWER SYSTEMS, V2, P513
[5]   EXPERIENCE WITH HVDC - TURBINE-GENERATOR TORSIONAL INTERACTION AT SQUARE BUTTE [J].
BAHRMAN, M ;
LARSEN, EV ;
PIWKO, RJ ;
PATEL, HS .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (03) :966-975
[6]  
Electrical Power Research Institute, 1982, EL2708 EPRI
[7]   CONTRIBUTION OF POWER-SYSTEM STABILIZERS TO THE DAMPING OF TORSIONAL OSCILLATIONS OF LARGE TURBOGENERATORS [J].
ELSERAFI, AM ;
NIAMAT, MY ;
HAQ, E .
ELECTRIC MACHINES AND POWER SYSTEMS, 1986, 11 (06) :451-464
[8]   DIGITAL-SIMULATION OF AN AC-DC SYSTEM IN DIRECT-PHASE QUANTITIES [J].
ELSERAFI, AM ;
SHEHATA, SA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (02) :731-742
[9]  
HAMMONS TJ, 1992, P INT C EL MACH MANC, V1, P69
[10]  
Horiuchi S., 1988, Electrical Engineering in Japan, V108, P60, DOI 10.1002/eej.4391080207