Pollution Flashover Performance of Full-scale ±800 kV Converter Station Post Insulators at High Altitude Area

被引:33
作者
Zhang, Chuyan [1 ]
Wang, Liming [1 ]
Guan, Zhicheng [1 ]
Zhang, Fuzeng [2 ]
机构
[1] Tsinghua Univ, Grad Sch Shenzhen, City Of Shenzhen 518055, Guangdong, Peoples R China
[2] China Southern Power Grid Co Ltd, Elect Power Res Inst, City Of Guangzhou 510080, Guangdong, Peoples R China
关键词
Pollution flashover performance; full-scale test sample; +/- 800 kV post insulators; high altitude area; artificial contamination test; CONTAMINATION PERFORMANCE; DC;
D O I
10.1109/TDEI.2013.6518940
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
On the background of the peculiar technology problems with the external insulation of UHV dc equipment in China, caused by high altitude and heavy pollution, this paper presents the pollution flashover performance of full-scale +/- 800 kV converter station post insulators at actual high altitude area. The tests were carried out according to the solid layer method, and the 50% withstand voltage (U-50%) was determined by the up-and-down method. The artificial contamination test results indicated that the shed configuration and the rod diameter had a significant influence on the flashover voltages. Shed parameters of one big and one small alternating shed composite post insulator which had superior dc pollution flashover performance had been recommended. The relationship between U-50% and insulation height was approximately linear at actual high altitude area for post insulators. It was found that partial discharges occurred at the top section firstly and partial arcs easily appeared at the parts nearby the connecting fittings during the flashover process. And arc floating phenomenon was significantly serious in actual high altitude area. Furthermore, comparison was made between the U-50% values of composite post insulators in fog and in rain. The U-50% values in fog of composite post insulators were generally higher than that in rain. Thus, the outdoor insulation design of composite post insulators should primarily consider the U-50% value in fog. This work thus provides useful reference for the design, operation and maintenance of UHV dc converter stations outdoor insulators in China.
引用
收藏
页码:717 / 726
页数:10
相关论文
共 25 条
[1]  
Alame N., 1992, IEEE 1992 Annual Report. Conference on Electrical Insulation and Dielectric Phenomena (Cat. No.92CH3123-7), P817, DOI 10.1109/CEIDP.1992.283195
[2]  
[Anonymous], 620732003 IECTS
[3]  
[Anonymous], 1982, TF57143 NGK
[4]   A COMPARISON OF HVAC AND HVDC CONTAMINATION PERFORMANCE OF STATION POST INSULATORS [J].
BAKER, AC ;
ZAFFANELLA, LE ;
ANZIVINO, LD ;
SCHNEIDER, HM ;
MORAN, JH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (02) :1486-1491
[5]   CONTAMINATION PERFORMANCE OF HVDC STATION POST INSULATORS [J].
BAKER, AC ;
ZAFFANELLA, LE ;
ANZIVINO, LD ;
SCHNEIDER, HM ;
MORAN, JH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1968-1975
[6]   EPRI-HVDC INSULATOR STUDIES .2. LABORATORY SIMULATION STUDIES [J].
CHENG, TC ;
WU, CT ;
KIM, YB ;
YOKOYAMA, S .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (02) :910-920
[7]   PERFORMANCE OF CONTAMINATED INSULATORS TESTED FROM 200 KV TO 1000 KV DC [J].
COMBER, MG ;
NIGBOR, RJ .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1981, 16 (03) :230-234
[8]  
Fan Jian-bin, 2007, Proceedings of the CSEE, V27, P1
[9]   A STUDY ON THE PROFILE OF HVDC INSULATORS - DC FLASHOVER PERFORMANCE [J].
FAZELIAN, M ;
WU, CY ;
CHENG, TC ;
NOUR, HI ;
WANG, LJ .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1989, 24 (01) :119-125
[10]  
Guan Zhicheng, 1999, Journal of Tsinghua University (Science and Technology), V39, P13