Estimation of Series Capacitance of an Actual, Uniform, Single, Isolated Transformer Winding from Measured Driving Point Impedance Data
被引:1
作者:
Biswas, Bidhan
[1
]
Bharadwaj, Nikhil
[1
]
Satish, L.
[1
]
机构:
[1] Indian Inst Sci, Dept Elect Engn, HV Lab, Bangalore 560012, Karnataka, India
来源:
4TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON 2019)
|
2019年
关键词:
Driving-Point-Impedance;
FRA;
Natural Frequency;
Series Capacitance;
Transformer Winding;
FREQUENCY-RESPONSE DATA;
D O I:
10.1109/CATCON47128.2019.CN0007
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
The authors' research group established in 2011 that series capacitance of a single, uniform, isolated transformer winding was indirectly measurable via the frequency response measurement. The present work is a sequel and proposes a relatively simpler estimation method. It is based on exploiting a unique property of the first few coefficients (viz., S-0, S-1, and s(2) terms) of the numerator and denominator polynomial of the driving point impedance (DPI) function, which is determined by curve-fitting the measured frequency response data. Essentially, the method solves a set of simultaneous equations which are formulated by equating pertinent coefficients of the fitted DPI(s) to the corresponding coefficients of the generalized expressions computed for an N-section ladder network. Going further, it is shown how the measured DPI data corresponding to the neutralopen and neutral-short cases can be usefully employed to cross-validate the estimated series capacitance. Experimental results on three different windings (viz., 2.2 kV/70 kVA continuous-disc, 33 kV/3.5 MVA continuous-disc, and a fully interleaved-disc) are presented to demonstrate the method's feasibility.
引用
收藏
页数:6
相关论文