Optimal controls of building storage systems using both ice storage and thermal mass - Part II: Parametric analysis

被引:54
作者
Hajiah, Ali [1 ]
Krarti, Moncef [2 ]
机构
[1] Kuwait Inst Sci Res, Bldg & Energy Technol Dept, Environm & Urban Dev Div, Kuwait, Kuwait
[2] Univ Colorado, Dept Civil Environm & Architectural Engn, Boulder, CO 80309 USA
关键词
Ice storage tank; Optimal control; Pre-cooling; Thermal mass; Thermal energy storage; ENERGY;
D O I
10.1016/j.enconman.2012.02.020
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents the results of a series of parametric analysis to investigate the factors that affect the effectiveness of using simultaneously building thermal capacitance and ice storage system to reduce total operating costs (including energy and demand costs) while maintaining adequate occupant comfort conditions in buildings. The analysis is based on a validated model-based simulation environment and includes several parameters including the optimization cost function, base chiller size, and ice storage tank capacity, and weather conditions. It found that the combined use of building thermal mass and active thermal energy storage system can save up to 40% of the total energy costs when integrated optimal control are considered to operate commercial buildings. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:509 / 515
页数:7
相关论文
共 16 条
  • [1] A near-optimal control strategy for cool storage systems with dynamic electric rates (RP-1252)
    Braun, James E.
    [J]. HVAC&R RESEARCH, 2007, 13 (04): : 557 - 580
  • [2] Drees K.H., 1996, HVAC&R Research, V2, P312, DOI DOI 10.1080/10789669.1996.10391352
  • [3] Energy and environmental economics, 2006, EN ENV EC SURV TIM O
  • [4] Hajiah A, 2011, J ENERGY MANAGE CONV
  • [5] Henze G.P., 1999, ASHRAE Transactions, V105, P553
  • [6] Henze G.P., 1997, HVAC&R RES, V3, P128
  • [7] Ice storage system controls for the reduction of operating cost and energy use
    Henze, GP
    Krarti, M
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1998, 120 (04): : 275 - 281
  • [8] Henze GP, 2009, ASME 3 INT C EN SUST
  • [9] Henze GP, 2008, ASHRAE TRAN, V114, P75
  • [10] Keeney K., 1996, HVACR Research, V2, P59, DOI [10.1080/10789669.1996.10391333, DOI 10.1080/10789669.1996.10391333]