Inactivation credit of UV radiation for viruses, bacteria and protozoan (oo)cysts in water: A review

被引:1143
作者
Hijnen, WAM [1 ]
Beerendonk, EF [1 ]
Medema, GJ [1 ]
机构
[1] Kiwa Water Res Ltd, NL-3430 BB Nieuwegein, Netherlands
关键词
UV irradiation; inactivation; kinetics; k-value; viruses; protozoa; bacteria; drinking water treatment;
D O I
10.1016/j.watres.2005.10.030
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
UV disinfection technology is of growing interest in the water industry since it was demonstrated that UV radiation is very effective against (oo)cysts of Cryptosporidium and Giardia, two pathogenic micro-organisms of major importance for the safety of drinking water. Quantitative Microbial Risk Assessment, the new concept for microbial safety of drinking water and wastewater, requires quantitative data of the inactivation or removal of pathogenic micro-organisms by water treatment processes. The objective of this study was to review the literature on UV disinfection and extract quantitative information about the relation between the inactivation of micro-organisms and the applied UV fluence. The quality of the available studies was evaluated and only high-quality studies were incorporated in the analysis of the inactivation kinetics. The results show that UV is effective against all waterborne pathogens. The inactivation of micro-organisms by UV could be described with first-order kinetics using fluence-inactivation data from laboratory studies in collimated beam tests. No inactivation at low fluences (offset) and/or no further increase of inactivation at higher fluences (tailing) was observed for some micro-organisms. Where observed, these were included in the description of the inactivation kinetics, even though the cause of tailing is still a matter of debate. The parameters that were used to describe inactivation are the inactivation rate constant k (cm(2)/mJ), the maximum inactivation demonstrated and (only for bacterial spores and Acanthamoeba) the offset value. These parameters were the basis for the calculation of the microbial inactivation credit (MIC = "log-credits") that can be assigned to a certain LTV fluence. The most LTV-resistant organisms are viruses, specifically Adenoviruses, and bacterial spores. The protozoon Acanthamoeba is also highly UV resistant. Bacteria and (oo)cysts of Cryptosporidium and Giardia are more susceptible with a fluence requirement of < 20 mJ/cm(2) for an MIC of 3 log. Several studies have reported an increased UV resistance of environmental bacteria and bacterial spores, compared to lab-grown strains. This means that higher UV fluences are required to obtain the same level of inactivation. Hence, for bacteria and spores, a correction factor of 2 and 4 was included in the MIC calculation, respectively, whereas some wastewater studies suggest that a correction of a factor of 7 is needed under these conditions. For phages and viruses this phenomenon appears to be of little significance and for protozoan (oo)cysts this aspect needs further investigation. Correction of the required fluence for DNA repair is considered unnecessary under the conditions of drinking water practice (no photo-repair, dark repair insignificant, esp. at higher (60 mJ/cm(2)) fluences) and probably also wastewater practice (photo-repair limited by light absorption). To enable accurate assessment of the effective fluence in continuous flow UV systems in water treatment practice, biodosimetry is still essential, although the use of computational fluid dynamics (CFD) improves the description of reactor hydraulics and fluence distribution. For UV systems that are primarily dedicated to inactivate the more sensitive pathogens (Cryptosporidium, Giardia, pathogenic bacteria), additional model organisms are needed to serve as biodosimeter. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:3 / 22
页数:20
相关论文
共 95 条
  • [31] Hoyer, 2004, P EUR C UV KARLSR UV
  • [32] HUSMAN AMD, 2003, 2 INT C ULTR TECHN V
  • [33] Removal of enteric viruses and selected microbial indicators by UV irradiation of secondary effluent
    Jacangelo, JG
    Loughran, P
    Petrik, B
    Simpson, D
    McIlroy, C
    [J]. WATER SCIENCE AND TECHNOLOGY, 2003, 47 (09) : 193 - 198
  • [34] UV inactivation of Cryptosporidium hominis as measured in cell culture
    Johnson, AM
    Linden, K
    Ciociola, KM
    De Leon, R
    Widmer, G
    Rochelle, PA
    [J]. APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 2005, 71 (05) : 2800 - 2802
  • [36] Kruithof J.C., 1992, J WATER SRT AQUA, V41, P88
  • [37] KRUITHOF JC, 2005, P 3 INT C ULTR TECHN
  • [38] UV disinfection of Giardia lamblia cysts in water
    Linden, KG
    Shin, GA
    Faubert, G
    Cairns, W
    Sobsey, MD
    [J]. ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2002, 36 (11) : 2519 - 2522
  • [39] ULTRAVIOLET DISINFECTION OF WASTE-WATER - EFFECT OF DOSE ON SUBSEQUENT PHOTOREACTIVATION
    LINDENAUER, KG
    DARBY, JL
    [J]. WATER RESEARCH, 1994, 28 (04) : 805 - 817
  • [40] HOST-CELL REACTIVATION IN MAMMALIAN CELLS .1. SURVIVAL OF ULTRA-VIOLET-IRRADIATED HERPES VIRUS IN DIFFERENT CELL-LINES
    LYTLE, CD
    [J]. INTERNATIONAL JOURNAL OF RADIATION BIOLOGY AND RELATED STUDIES IN PHYSICS CHEMISTRY AND MEDICINE, 1971, 19 (04): : 329 - &