Experimental study on air cooling by spray in the upstream flow of a heat exchanger

被引:36
作者
Tissot, J. [1 ]
Boulet, P. [1 ]
Labergue, A. [1 ]
Castanet, G. [1 ]
Trinquet, F. [2 ]
Fournaison, L. [2 ]
机构
[1] Nancy Univ, LEMTA, CNRS, Fac Sci & Tech, F-54506 Vandoeuvre Les Nancy, France
[2] GPAN, Lab Genie Proc Environm Energie & Sante LGP2ES EA, F-92761 Antony, France
关键词
Spray; Cooling; Evaporation; Heat transfer; CONDENSER; SYSTEM;
D O I
10.1016/j.ijthermalsci.2012.06.005
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental study has been carried out on a water sprayed air flow aimed at cooling the air upstream of a heat exchanger in order to improve the heat transfer. A pilot has been built allowing injecting droplets in air in various conditions while controlling flow rates, temperature and humidity. The emphasis has been put on the spray evaporation resulting in a temperature decrease and humidity increase in the air flow. An actual increase in the heat exchanged (up to 3 times more) for an air initially entering in surrounding conditions (temperature between 293 and 308 K and relative humidity between 47.5% and 19.7%) has been reached when injecting upstream droplets smaller than 25 pm, in an air flow crossing the exchanger. A validation of a numerical study on the heat exchanges in the air flow has been also achieved. Results will be applied for the optimization of the water flow providing the best compromise between heat exchanged and water consumption. (C) 2012 Elsevier Masson SAS. All rights reserved.
引用
收藏
页码:23 / 31
页数:9
相关论文
共 8 条
[1]   ANALYSIS OF SPRAY-COOLED FINNED-TUBE HEAT-EXCHANGERS [J].
DREYER, AA ;
KRIEL, DE ;
ERENS, PJ .
HEAT TRANSFER ENGINEERING, 1992, 13 (04) :53-71
[2]   Performance improvement of air-cooled refrigeration system by using evaporatively cooled air condenser [J].
Hajidavalloo, E. ;
Eghtedari, H. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (05) :982-988
[3]  
J Tissot, 2011, THESIS U HENRI POINC
[4]   HEAT-TRANSFER FROM TUBE BANKS TO AIR WATER MIST FLOW [J].
NAKAYAMA, W ;
KUWAHARA, H ;
HIRASAWA, S .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1988, 31 (02) :449-460
[5]   Air cooling by evaporating droplets in the upward flow of a condenser [J].
Tissot, J. ;
Boulet, P. ;
Trinquet, F. ;
Fournaison, L. ;
Macchi-Tejeda, H. .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (11) :2122-2131
[6]   Incorporated evaporative condenser [J].
Vrachopoulos, Michalis Gr. ;
Filios, Andronikos E. ;
Kotsiovelos, Georgios T. ;
Kravvaritis, Eleftherios D. .
APPLIED THERMAL ENGINEERING, 2007, 27 (5-6) :823-828
[7]   Numerical model of sprayed air cooled condenser coupled to refrigerating system [J].
Youbi-Idrissi, M. ;
Macchi-Tejeda, H. ;
Fournaison, L. ;
Guilpart, J. .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (07) :1943-1951
[8]   Improved energy performance of air-cooled chiller system with mist pre-cooling Mist improvement on air-cooled chillers [J].
Yu, F. W. ;
Chan, K. T. .
APPLIED THERMAL ENGINEERING, 2011, 31 (04) :537-544