Influence of constructive parameters on the performance of two indirect evaporative cooler prototypes

被引:26
作者
Tejero-Gonzalez, Ana [1 ]
Andres-Chicote, Manuel [1 ]
Velasco-Gomez, Eloy [1 ]
Javier Rey-Martinez, Francisco [1 ]
机构
[1] Univ Valladolid, Sch Engn, Dept Energy & Fluidmech, E-47011 Valladolid, Spain
关键词
Indirect evaporative cooling; Heat recovery; Plastic heat exchanger; Heat exchange area; Cooling capacity; Thermal conductance; ENERGY RECOVERY-SYSTEM; HEAT;
D O I
10.1016/j.applthermaleng.2012.10.054
中图分类号
O414.1 [热力学];
学科分类号
摘要
Two equally-sized cross-flow heat-exchanger prototypes have been designed with a total heat exchange area of 6 m(2) and 3 m(2) respectively, constructed with polycarbonate hollow panels of different cross section. They are connected into a heat-recovery cycle within the whole experimental setup constructed for the tests, which mainly consists of: an Air Handling Unit to simulate the outdoor airstream conditions, a conditioned climate chamber, and a water circuit to provide the water supply required. They have been experimentally characterised in two operating modes in order to determine how evaporative cooling improves heat recovery in each case, focussing on the influence of modifying the constructive characteristics. To perform the evaporative cooling process, water is supplied to the exhaust airstream. Results are studied considering how constructive issues, outdoor air volume flow rate and temperature, as well as operating mode influence on the performance obtained. An Analysis of Variance shows how outdoor airflow has a key role in the performance of the systems; whereas entering outdoor air temperature determines cooling capacities. Improvements introduced by larger heat exchange areas compensate with their corresponding smaller cross sections, which hinder water-air distribution on the exhaust air side of the heat exchanger. Finally, these small devices achieve cooling capacities of up to 800W, being able to partly support ventilation load and achieving around 50% of energy saving in ventilation cooling. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1017 / 1025
页数:9
相关论文
共 22 条
[1]  
Alvarez-Guerra Plasencia M.A., 2000, TECHNICAL DOCUMENTS
[2]  
ASHRAE, 2000, ASHRAE HDB SYST EQ
[3]  
ASHRAE, 2000, ASHRAE HDB 2000 SYST
[4]   Energy saving potential of an indirect evaporative cooler as a pre-cooling unit for mechanical cooling systems in Iran [J].
Delfani, Shahram ;
Esmaeelian, Jafar ;
Pasdarshahri, Hadi ;
Karami, Maryam .
ENERGY AND BUILDINGS, 2010, 42 (11) :2169-2176
[5]   Speculation in the feasibility of evaporative cooling [J].
El-Refaie, M. F. ;
Kaseb, S. .
BUILDING AND ENVIRONMENT, 2009, 44 (04) :826-838
[6]   Experimental investigation of two-stage indirect/direct evaporative cooling system in various climatic conditions [J].
Heidarinejad, Ghassem ;
Bozorgmehr, Mojtaba ;
Delfani, Shahram ;
Esmaeelian, Jafar .
BUILDING AND ENVIRONMENT, 2009, 44 (10) :2073-2079
[7]   A review of sustainable cooling technologies in buildings [J].
Hughes, Ben Richard ;
Chaudhry, Hassam Nasarullah ;
Ghani, Saud Abdul .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2011, 15 (06) :3112-3120
[8]   Energy Recovery System in Mediterranean region [J].
Jaber, Samar ;
Ajibb, Salman .
SUSTAINABLE CITIES AND SOCIETY, 2012, 3 :24-29
[9]  
Joen CT, 2009, INT J REFRIG, V32, P763, DOI DOI 10.1016/J.IJREFRIG.2008.11.008
[10]  
Kays W.M., 1984, COMPACT HEAT EXCHANG, V3rd