Current transformer (CT);
finite-element method (FEM);
short-time rating;
SINGLE;
D O I:
10.1109/TPWRD.2008.2007008
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
Closed form expressions and a finite-element method are used to compute the maximum force in the primary conductor of a wound current transformer (CT). It is shown that for a given volume for the primary winding, one configuration exists that leads to a maximum force. It is proved that the mechanical short-time rating of two CTs having different turns but identical ampere turns is not equivalent. Designers can now establish and test a CT with a worst-case configuration.