Study on flow boiling heat transfer characteristics of R161/oil mixture inside horizontal micro-fin tube

被引:29
作者
Han, X. H. [1 ]
Fang, Y. B. [1 ]
Wu, M. [1 ]
Qiao, X. G. [2 ]
Chen, G. M. [1 ]
机构
[1] Zhejiang Univ, Inst Refrigerat & Cryogen, Hangzhou 310027, Zhejiang, Peoples R China
[2] Zhejiang Coll Construct, Hangzhou 311321, Zhejiang, Peoples R China
关键词
R161; Oil; Boiling heat transfer; Micro-fin tube; Correlation; PART I; ALTERNATIVE REFRIGERANT; PRESSURE-DROP; OIL; EVAPORATION; REPLACEMENT; MISCIBILITY; PERFORMANCE; SOLUBILITY; VISCOSITY;
D O I
10.1016/j.ijheatmasstransfer.2016.08.043
中图分类号
O414.1 [热力学];
学科分类号
摘要
The research on alternative refrigerants has been one of the urgent issues in the refrigeration and air conditioning industry for the sake of reducing ozone depletion and global warming effect. R161, as a refrigerant with good environmental acceptability (GWP = 12, ODP = 0), good thermo-physical properties, good heat transfer and flow characteristics, and highly similar thermo-physical properties to R22, has attracted broad attention as a substitute of R22 and R407C. In this paper, the boiling heat transfer and pressure drop characteristics of R161/POE mixture in a 7 mm O.D. horizontal micro-fin tube were investigated by experimental methods. The local heat transfer coefficients and pressure drops were measured at mass flux range of (100 similar to 250) kg/(m(2).s), heat flux range of (11.76 similar to 52.94) kW/m(2), bubble point temperature range of (-5 similar to 8) degrees C, and oil concentration range of (0 similar to 5)%. The results showed that: (1) at low vapor quality region, the local heat transfer coefficient increased with oil concentration, while at the high vapor quality region, it decreased rapidly with the increase of oil concentration; (2) the pressure drop increased with the increase of oil concentration, mass flux and heat flux; (3) the influence of oil on heat transfer coefficient and pressure drop decreased with the increase of mass flux. A new correlation to predict the local boiling heat transfer of R161/oil mixture inside small micro-fin tubes was developed on the basis of the local properties of refrigerant/oil mixture and structure of enhanced tube, and the predicted data agreed with the experimental data within the deviations of (-15 similar to+20)%. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:276 / 287
页数:12
相关论文
共 53 条
[1]  
[Anonymous], 1987, MONTR PROT SUBST DEP
[2]  
Calm JM, 2004, ASHRAE J, V46, P29
[3]  
Cavallini A., 1999, 20 INT C REFR
[4]   CORRELATION FOR BOILING HEAT TRANSFER TO SATURATED FLUIDS IN CONVECTIVE FLOW [J].
CHEN, JC .
INDUSTRIAL & ENGINEERING CHEMISTRY PROCESS DESIGN AND DEVELOPMENT, 1966, 5 (03) :322-&
[5]   Estimation of thermophysical properties of lubricating oils and their solutions with refrigerants: An appraisal of existing methods [J].
Conde, MR .
APPLIED THERMAL ENGINEERING, 1996, 16 (01) :51-61
[6]   Performance assessment of HC-290 as a drop-in substitute to HCFC-22 in a window air conditioner [J].
Devotta, S ;
Padalkar, AS ;
Sane, NK .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (04) :594-604
[7]  
Didi MBO, 2002, INT J REFRIG, V25, P935
[8]  
[丁睿 DING Rui], 2006, [流体机械, Fluid Machinery], V34, P80
[9]  
Dittus F. W., 1930, PUBLICATIONS ENG
[10]  
ECKELS SJ, 1991, ASHRAE TRAN, V97, P71