Performance of Interconnection Protection Based on Distance Relaying for Wind Power Distributed Generation

被引:62
作者
El-Arroudi, Khalil [1 ]
Joos, Geza [1 ]
机构
[1] McGill Univ, Dept Elect & Comp Engn, Montreal, PQ H3A 2A7, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Power systems; distributed power generation; distribution systems; power system protection; power system faults; wind energy; IMPACT;
D O I
10.1109/TPWRD.2017.2693292
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a method to analyze and improve the performance of interconnection protection based on distance relaying for wind power distributed generation (DC) in distribution systems. Of particular importance is distance protection that uses the concept of prefault voltages as reference quantities found to have issues with intermittent behavior of wind power DC. This concept is normally used in different distance protective relaying applications in order to increase the fault resistance coverage capability of the distance relays as well as to ensure selectivity, dependability, and security under extreme undervoltages. The main contributions of this paper are to analyze this issue and propose a method to enhance the performance of distance protection to mitigate this issue. In this methodology, several case studies are investigated with different penetration levels, weather patterns, and configuration topology of DCs under both normal operating conditions as well as fault conditions. Results for a case study are given.
引用
收藏
页码:620 / 629
页数:10
相关论文
共 33 条
  • [1] Anderson P.M., 1999, Power system protection
  • [2] [Anonymous], PROTECTIVE RELAYING
  • [3] [Anonymous], 2012, Long-Term Wind Power Variability
  • [4] [Anonymous], 2010, 10 IET INT C DEV POW
  • [5] [Anonymous], SIMPOWERSYSTEMS SIM
  • [6] [Anonymous], P W PROT REL C SPOK
  • [7] [Anonymous], 2010, P IEEE PES GEN M
  • [8] [Anonymous], POWER SYSTEM PROTECT
  • [9] [Anonymous], B534 CIGRE
  • [10] [Anonymous], 2004, 61850 IEC