Study on Impulse Flashover Characteristics of Polluted Insulators Under Different Voltage Applied Methods

被引:0
作者
Bo, Peng [1 ]
Huang Fu-yong [1 ]
Zhou Wei-hua [1 ]
Tang Mei-yun [2 ]
Cheng, Wang [1 ]
Feng, Wang [1 ]
Chao Yafeng [1 ]
机构
[1] Hunan Elect Power Corp, Res Inst, Changsha 410007, Hunan, Peoples R China
[2] Hunan Elect Power Corp, Changsha 410007, Hunan, Peoples R China
来源
2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP) | 2013年
关键词
polluted insulators; Impulse Flashover Characteristics partial drying effect; power frequency pre-discharge effect; impulse voltage superimposed on power frequency; PORCELAIN; MODEL;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Pollution flashover of insulator strings is one of the most serious natural disasters in transmission line, and it is dangerous to the power grid. The three voltage applied methods of impulse voltage, power frequency pre-voltage and impulse voltage superimposed on power frequency were built to do the research, and influence of power frequency pre-voltage, partial drying effect of power frequency leakage current on impulse flashover characteristics were studied in the paper. For a fixed NSDD, the impulse flashover voltage of three test methods increased with the increasing of ESDD, the positive polarity impulse flashover voltage was lower than that of negative polarity ones. During the process of impulse voltage superimposed on power frequency test method, the power frequency voltage upraise the initial potential of impulse flashover voltage, and it was conducive to the flashover of polluted insulators. During the process of impulse voltage superimposed on power frequency test, drying effect due to power frequency current and power frequency pre-discharge effect were helpful to the form of partial discharge arc, and they provided favorable environments for the flashover of polluted insulators. Pre-discharge of power frequency and drying effect of power frequency current was contributed to the flashover of polluted insulators, and it was more and more clearly with the increasing of pollution, at a special point both pre-discharge of power frequency and drying effect of power frequency current were in a state of equilibrium.
引用
收藏
页码:342 / 346
页数:5
相关论文
共 18 条
[1]  
[Anonymous], 1979, Electra, P117
[2]  
[Anonymous], 2004, 60815 IEC CIGRE WORK
[3]  
CIGRE Working Group 33-04, 1992, 330404 CIGRE, V140, P99
[4]   POLLUTED INSULATOR FLASHOVER MODEL FOR AC VOLTAGE [J].
GHOSH, PS ;
CHATTERJEE, N .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (01) :128-136
[5]  
Gu L., 1990, POLLUTED INSULATION
[6]   MULTISTORY TRANSMISSION TOWER MODEL FOR LIGHTNING SURGE ANALYSIS [J].
ISHII, M ;
KAWAMURA, T ;
KOUNO, T ;
OHSAKI, E ;
SHIOKAWA, K ;
MUROTANI, K ;
HIGUCHI, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (03) :1327-1335
[7]  
Jiang X., 2009, POLLUTION ICE COATED
[8]  
Jiang Xing-liang, 2006, Proceedings of the CSEE, V26, P24
[9]   Comparison of DC pollution flashover performances of various types of porcelain, glass, and composite insulators [J].
Jiang, Xingliang ;
Yuan, Jihe ;
Shu, Lichun ;
Zhang, Zhijin ;
Hu, Jianlin ;
Mao, Feng .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :1183-1190
[10]   VARIABLE-VOLTAGE APPLICATION FOR INSULATOR POLLUTION TESTS [J].
LAMBETH, PJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :2103-2111