Smoke flow in full-scale urban road tunnel fires with large cross-sectional vertical shafts

被引:29
作者
Guo, Qinghua [2 ,3 ]
Zhu, Hehua [1 ,2 ]
Zhang, Yuxin [2 ,3 ]
Shen, Yi [2 ,3 ]
Zhang, Yinping [4 ]
Yan, Zhiguo [1 ,2 ]
机构
[1] Tongji Univ, State Key Lab Disaster Reduct Civil Engn, 1239 Siping Rd, Shanghai 200092, Peoples R China
[2] Tongji Univ, Dept Geotech Engn, 1239 Siping Rd, Shanghai 200092, Peoples R China
[3] Tongji Univ, Key Lab Geotech & Underground Engn, Minist Educ, 1239 Siping Rd, Shanghai 200092, Peoples R China
[4] Shanghai Urban Construct Design & Res Inst Grp Co, 3447 Dongfang Rd, Shanghai 200125, Peoples R China
关键词
Full-scale; Tunnel fire; Smoke spread; Vertical shafts; NATURAL VENTILATION PERFORMANCE; LARGE-EDDY SIMULATION; BOARD-COUPLED SHAFT; BACK-LAYERING FLOW; TEMPERATURE DISTRIBUTION; ASPECT RATIO; EXTERNAL WIND; EXTRACTION; VELOCITY; LENGTH;
D O I
10.1016/j.tust.2020.103536
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, a series of full-scale fire tests are performed in a tunnel with large cross-sectional vertical shafts. The heat release rates and fire locations are considered, and the general smoke development, smoke flow pattern in the shaft, smoke temperature distribution, and smoke front velocity are analysed. It is found that complete plug-holing occurs in the tunnel with large cross-sectional vertical shafts. The smoke flows into the shaft from the bottom sides and spreads out along the shaft sidewalls. The smoke cannot fill the shaft cross-section, even at the shaft outlet. In the early and full-development stages of a fire, a well-stratified smoke layer exists, whereas in the decay stage and after burning out, the visibility significantly reduces. The smoke can be controlled within 80-125 m on each side of the fire source, and it takes approximately 10 min for the visibility to self-recover naturally for common car fires after burning out. The results of the full-scale experiment indicate that the shaft has acceptable performance in smoke control for the test scenario investigated. According to an analysis of the tunnel environment during a common car fire, as well as the evacuation movement, it can be concluded that the occupants can escape safely. The experimental results are used to verify the smoke control performance of the vertical shaft and provide guidance for the design of naturally ventilated tunnels with vertical shafts.
引用
收藏
页数:15
相关论文
共 58 条
[1]  
Anghel I, 2017, ACTA TECH NAPOC SER-, V60, P217
[2]   ESTIMATING LARGE POOL FIRE BURNING RATES [J].
BABRAUSKAS, V .
FIRE TECHNOLOGY, 1983, 19 (04) :251-261
[3]   Experimental study on the effect of heat release rate and aspect ratio of tunnel on the plug-holing phenomena in shallow underground tunnels [J].
Baek, Dabin ;
Sung, Kun Hyuk ;
Ryou, Hong Sun .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 113 :1135-1141
[4]   Improvement in smoke extraction efficiency by natural ventilation through a board-coupled shaft during tunnel fires [J].
Cong, H. Y. ;
Wang, X. S. ;
Zhu, P. ;
Jiang, T. H. ;
Shi, X. J. .
APPLIED THERMAL ENGINEERING, 2017, 118 :127-137
[5]   Experimental and theoretical studies on the heat extraction performance by natural ventilation with a board-coupled shaft during tunnel fires [J].
Cong, Haiyong ;
Bi, Mingshu ;
Zhang, Shulin ;
Li, Bei ;
Ren, Jingjie ;
Gao, Wei .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2019, 141 (96-102) :96-102
[6]   Effects of vertical shaft arrangement on natural ventilation performance during tunnel fires [J].
Fan, C. G. ;
Ji, J. ;
Wang, W. ;
Sun, J. H. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 73 :158-169
[7]   Experimental study of air entrainment mode with natural ventilation using shafts in road tunnel fires [J].
Fan, C. G. ;
Ji, J. ;
Gao, Z. H. ;
Han, J. Y. ;
Sun, J. H. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 56 (1-2) :750-757
[8]  
Fan C.G., COMBUST SCI TECHNOL, P1
[9]  
Fan C.G., 2018, FIRE MATERICALS, P1
[10]  
Fan C.G., 2019, FIRE MATERICALS, P1