Model scale tunnel tests with water spray

被引:45
作者
Ingason, Haukur [1 ]
机构
[1] SP Tech Res Inst Sweden, S-50115 Boras, Sweden
关键词
tunnel; model scale; water spray;
D O I
10.1016/j.firesaf.2007.12.002
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A model scale study (1:23) was carried out in order to improve the basic understanding of water spray systems ill longitudinal tunnel flow. The water spray system consisted of commercially available axial-flow hollow cone nozzles. Tests with both a deluge system made of 12 nozzles placed directly above the fire source and a water curtain system consisting of four nozzles placed either downstream or upstream of the fire source were carried out. A wood crib was used to stimulate the fire source, which was designed to correspond to a HGV (heavy goods vehicle) fire load in large scale. A second wood crib was used as a target pile and was placed downstream the ignited wood crib. The parameters varied were the water flow rate and water pressure, the longitudinal ventilation rate and the arrangement of the nozzle system. Possible fire spread between wood cribs, with a free distance corresponding to 15 m in large scale, was investigated. (C) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:512 / 528
页数:17
相关论文
共 33 条
[1]  
Beard A., 2012, Handbook of Tunnel Fire Safety, VSecond
[2]  
BRANDT AW, 2005, F05108 SINTEF NBL
[3]   Fire suppression by water sprays [J].
Grant, G ;
Brenton, J ;
Drysdale, D .
PROGRESS IN ENERGY AND COMBUSTION SCIENCE, 2000, 26 (02) :79-130
[4]  
Guigas X., 2004, P 5 INT C TUNN FIR 2, P261
[5]  
HESKESTAD G, 1980, J FIRE FLAMMABILITY, V11, P254
[6]   Extinction of gas and liquid pool fires with water sprays [J].
Heskestad, G .
FIRE SAFETY JOURNAL, 2003, 38 (04) :301-317
[7]   Scaling the interaction of water sprays and flames [J].
Heskestad, G .
FIRE SAFETY JOURNAL, 2002, 37 (06) :535-548
[8]  
Heskestad G., 1975, J FIRE FLAMMABILITY, V6, P253
[9]  
Heskestad G., 1972, P 14 S INT COMB PENN, P1021
[10]   Heat release rates from heavy goods vehicle trailer fires in tunnels [J].
Ingason, H ;
Lönnermark, A .
FIRE SAFETY JOURNAL, 2005, 40 (07) :646-668