Experimental study on the stability of the transmission tower with hybrid slab foundation

被引:8
作者
Yuan, Guanglin [1 ]
Yang, Biao [1 ]
Huang, Zhaohui [2 ]
Tan, Xiaozhe [1 ]
机构
[1] China Univ Min & Technol, Sch Mech & Civil Engn, State Key Lab Geomech & Deep Underground Engn, Xuzhou 221116, Jiangsu, Peoples R China
[2] Brunel Univ, Dept Civil & Environm Engn, Coll Engn Design & Phys Sci, Uxbridge UB8 3PH, Middx, England
关键词
Power transmission tower; Hybrid slab foundation; Ground movements; Scaled tower model; LINE TOWERS; FAILURE ANALYSIS; PERFORMANCE; WIND; DEFORMATION; BEHAVIOR;
D O I
10.1016/j.engstruct.2018.01.066
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this paper, a 1:5 scaled tower model for a typical 220 kV single-circuit power transmission tower with hybrid slab foundation has been designed and tested. The scaled tower model was tested under the movement of horizontal ground surface stretching with normal working loading conditions. One of the main objectives of this research is to investigate the stability of the power transmission tower subjected to horizontal ground movement by using hybrid slab foundation. The deformations of the tested tower model and stresses and strains within the different structural members of the tower and the reinforced concrete slab of the foundation have been fully measured. A large mount comprehensive test data has been generated. The research clearly indicated that compared to the isolated tower leg's foundation the proposed hybrid slab foundation has very good resistance, in terms of truss members' deformations and stresses, to the ground movement.
引用
收藏
页码:151 / 165
页数:15
相关论文
共 19 条
  • [1] Failure analysis of transmission towersd
    Albermani, F.
    Kitipornchai, S.
    Chan, R. W. K.
    [J]. ENGINEERING FAILURE ANALYSIS, 2009, 16 (06) : 1922 - 1928
  • [2] Dynamic behavior and stability of transmission line towers under wind forces
    Battista, RC
    Rodrigues, RS
    Pfeil, MS
    [J]. JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2003, 91 (08) : 1051 - 1067
  • [3] Bruhn R. W., 1991, P 10 INT C GROUND CO, P301
  • [4] Behaviour of guyed transmission line structures under tornado wind loading
    Hamada, A.
    El Damatty, A. A.
    [J]. COMPUTERS & STRUCTURES, 2011, 89 (11-12) : 986 - 1003
  • [5] Jia L., 2015, DESIGN OPERATION POW
  • [6] Safety of power transmission line structures under wind and ice storms
    Kudzys, A
    [J]. ENGINEERING STRUCTURES, 2006, 28 (05) : 682 - 689
  • [7] Improved Performance of Electrical Transmission Tower Structure Using Connected Foundation in Soft Ground
    Kyung, Doohyun
    Choi, Youngho
    Jeong, Sangseom
    Lee, Junhwan
    [J]. ENERGIES, 2015, 8 (06): : 4963 - 4982
  • [8] Finite Element Analysis of Foundation Settlement of 220kv Transmission Tower with Independent Foundation
    Li, Bo
    Jian, Mingjian
    Zhang, Duqing
    Zhang, Guangcheng
    [J]. ADVANCES IN ENGINEERING DESIGN AND OPTIMIZATION III, PTS 1 AND 2, 2012, 201-202 : 602 - 607
  • [9] Performance evaluation of a transmission tower by substructure test
    Moon, Byoung-Wook
    Park, Ji-Hun
    Lee, Sung-Kyung
    Kim, Jinkoo
    Kim, Taejin
    Min, Kyung-Won
    [J]. JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2009, 65 (01) : 1 - 11
  • [10] Studies on failure of transmission line towers in testing
    Rao, N. Prasad
    Knight, G. M. Samuel
    Mohan, S. J.
    Lakshmanan, N.
    [J]. ENGINEERING STRUCTURES, 2012, 35 : 55 - 70