Interruption Behaviours with 84/72-kV VCB and GCB

被引:0
作者
Tokoyoda, Sho [1 ]
Takeda, Toshinobu [1 ]
Kamei, Kenji [1 ]
Yoshida, Daisuke [1 ]
Ito, Hiraki [1 ]
机构
[1] Mitsubishi Electr Corp, Transmiss & Distribut Syst Ctr, Amagasaki, Hyogo 6618661, Japan
来源
2013 2ND INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST) | 2013年
关键词
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The interruption behaviours of a high voltage vacuum circuit breaker (VCB) have been investigated in detail [1]-[3]. A VCB has several specific interruption behaviours compared to an SF6 gas circuit breaker (GCB). In particular, a higher thermal interruption capability and a high frequency (HF) re-ignition and HF interruption phenomena might cause switching overvoltage. Interruption behaviours such as the chopping characteristic and HF re-ignition and HF interruption behaviours were measured in this study under the same testing conditions as for several current interruption testing duties using a model VCB and GCB with the same rated voltage of 84/72 kV. The results show that the current chopping level of the VCB is relatively low, so any overvoltage due to current chopping when using a HV-VCB does not significantly influence transmission networks. However, HV-VCB iterates the HF re-ignitions and HF interruptions during the half cycle of inductive current (180-700 A) switching tests and additional large current switching tests. Therefore, HV-VCB may generate steep overvoltages, which may affect the protection relay and secondary equipment operations.